Two classic failures turn up again and again when motors are selected on site. The first is copying the nameplate off an old machine when the new duty has higher air flow or head, so the motor runs hot at the edge of full load all day. The second is selecting big for safety — hanging a 22 kW unit on an 11 kW job, where light-load operation drops both the power factor and the efficiency, wastes electricity and eats cabinet space.
Selecting the power of a three-phase induction motor is essentially about working out the shaft power the load really needs, applying a sensible margin, and rounding to a standard rating. The difficulty is all in the first step: the formula depends completely on the load type. Constant-torque loads work from torque and speed; fan and pump loads work from flow and pressure or head. The two cannot share a formula.
The arithmetic usually goes wrong here:
| Parameter | Meaning | Unit | Notes |
|---|---|---|---|
| P | Load shaft power | kW | Useful power calculated on the load side |
| T | Load torque | N·m | For constant-torque loads |
| n | Load speed | r/min | At the same duty point as T |
| Q | Air flow / flow rate | m³/s | m³/h must be divided by 3600 |
| p | Fan total pressure | Pa | Pressure difference across inlet and outlet |
| H | Pump head | m | Including static head and pipe losses |
| ρ | Medium density | kg/m³ | 1000 for water, 1.2 for air |
| η | Fan / pump efficiency | — | Typically 0.6–0.8 |
| η_c | Transmission efficiency | — | 1.0 direct drive, 0.95 belt |
| K | Margin factor | — | See the table below |
Margin factor K:
| Load type | K |
|---|---|
| Constant torque, steady load | 1.1–1.2 |
| Fan duty (centrifugal fan) | 1.1–1.15 |
| Pump duty | 1.15–1.2 |
| Shock loads, frequent starting | 1.3–1.5 |
Example A — Centrifugal fan
Given: air flow Q = 12000 m³/h, total pressure p = 1800 Pa, fan efficiency η = 0.75, direct drive η_c = 1.0, margin factor K = 1.15.
Step 1: Unify units. Q = 12000/3600 = 3.333 m³/s.
Step 2: Shaft power. P = Q·p/(1000·η) = 3.333×1800/(1000×0.75) = 8.0 kW.
Step 3: Apply the margin. P_m ≥ 1.15×8.0 = 9.2 kW.
Result: round to a standard rating and select an 11 kW three-phase induction motor. Re-checking with the head form (air ρ = 1.2, H = p/(ρg) = 152.9 m): P = ρgQH/(1000η) = 1.2×9.81×3.333×152.9/750 = 8.0 kW — the two methods agree.
Example B — Centrifugal pump
Given: flow Q = 50 m³/h, head H = 32 m, medium water ρ = 1000 kg/m³, pump efficiency η = 0.70, belt drive η_c = 0.95, K = 1.15.
Step 1: Unify units. Q = 50/3600 = 0.01389 m³/s.
Step 2: Pump shaft power. P = ρgQH/(1000η) = 1000×9.81×0.01389×32/(1000×0.70) = 6.23 kW.
Step 3: Divide by the transmission efficiency. Motor output required P_L = 6.23/0.95 = 6.56 kW.
Step 4: Apply the margin. P_m ≥ 1.15×6.56 = 7.54 kW.
Result: select a standard 7.5 kW motor. The margin is only 7.54/6.56 ≈ 1.15, right on the line. If the flow and head fluctuate appreciably, go to 11 kW so the motor does not run hot at full load for long periods.