Three-Phase Induction Motor Power Selection: P = Q·H·ρ·g/(1000·η) for Fans and Pumps

1. An undersized motor burns out; an oversized motor wastes money

Two classic failures turn up again and again when motors are selected on site. The first is copying the nameplate off an old machine when the new duty has higher air flow or head, so the motor runs hot at the edge of full load all day. The second is selecting big for safety — hanging a 22 kW unit on an 11 kW job, where light-load operation drops both the power factor and the efficiency, wastes electricity and eats cabinet space.

Selecting the power of a three-phase induction motor is essentially about working out the shaft power the load really needs, applying a sensible margin, and rounding to a standard rating. The difficulty is all in the first step: the formula depends completely on the load type. Constant-torque loads work from torque and speed; fan and pump loads work from flow and pressure or head. The two cannot share a formula.

The arithmetic usually goes wrong here:

2. Formulas and parameters

Constant-torque shaft power: P = T·n/9550 (kW, T in N·m)
Fan shaft power: P = Q·p/(1000·η)
Pump shaft power: P = Q·H·ρ·g/(1000·η)
Required motor power: P_m ≥ K·P/η_c
ParameterMeaningUnitNotes
PLoad shaft powerkWUseful power calculated on the load side
TLoad torqueN·mFor constant-torque loads
nLoad speedr/minAt the same duty point as T
QAir flow / flow ratem³/sm³/h must be divided by 3600
pFan total pressurePaPressure difference across inlet and outlet
HPump headmIncluding static head and pipe losses
ρMedium densitykg/m³1000 for water, 1.2 for air
ηFan / pump efficiency—Typically 0.6–0.8
η_cTransmission efficiency—1.0 direct drive, 0.95 belt
KMargin factor—See the table below

Margin factor K:

Load typeK
Constant torque, steady load1.1–1.2
Fan duty (centrifugal fan)1.1–1.15
Pump duty1.15–1.2
Shock loads, frequent starting1.3–1.5
💡 Practical tip:Fan and pump power varies with the cube of speed, P ∝ n³. Dropping the speed to 80 % with a VFD leaves roughly half the power. Such loads are better served by a VFD-duty motor than by going one size up at full-line frequency.
💡 Practical tip:Pump selection must follow the actual operating point on the flow-head curve. Multiplying maximum flow by maximum head inflates the shaft power by more than 40 %.
⚠️ Caution:A motor is rated on output shaft power. If P on the load side is the useful fluid power, two stages of loss — fan or pump efficiency and transmission efficiency — still sit in between and must be divided out one by one.

3. Worked examples

Example A — Centrifugal fan

Given: air flow Q = 12000 m³/h, total pressure p = 1800 Pa, fan efficiency η = 0.75, direct drive η_c = 1.0, margin factor K = 1.15.

Step 1: Unify units. Q = 12000/3600 = 3.333 m³/s.

Step 2: Shaft power. P = Q·p/(1000·η) = 3.333×1800/(1000×0.75) = 8.0 kW.

Step 3: Apply the margin. P_m ≥ 1.15×8.0 = 9.2 kW.

Result: round to a standard rating and select an 11 kW three-phase induction motor. Re-checking with the head form (air ρ = 1.2, H = p/(ρg) = 152.9 m): P = ρgQH/(1000η) = 1.2×9.81×3.333×152.9/750 = 8.0 kW — the two methods agree.

Example B — Centrifugal pump

Given: flow Q = 50 m³/h, head H = 32 m, medium water ρ = 1000 kg/m³, pump efficiency η = 0.70, belt drive η_c = 0.95, K = 1.15.

Step 1: Unify units. Q = 50/3600 = 0.01389 m³/s.

Step 2: Pump shaft power. P = ρgQH/(1000η) = 1000×9.81×0.01389×32/(1000×0.70) = 6.23 kW.

Step 3: Divide by the transmission efficiency. Motor output required P_L = 6.23/0.95 = 6.56 kW.

Step 4: Apply the margin. P_m ≥ 1.15×6.56 = 7.54 kW.

Result: select a standard 7.5 kW motor. The margin is only 7.54/6.56 ≈ 1.15, right on the line. If the flow and head fluctuate appreciably, go to 11 kW so the motor does not run hot at full load for long periods.

4. Common mistakes and cautions

📖 Next up:with the motor power settled, a reducer still stands between the motor and the driven end — the next piece covers how to select harmonic and RV reducers, focusing on rated torque, average load torque and backlash.