How do you switch a Mitsubishi FX analog module between voltage and current input?

Voltage and current are not two "modes" you flip with a single command. Two things change together: which terminal the transmitter lands on decides the physical quantity, and the channel setting decides which range the module uses to interpret it. Change only one and the reading will certainly be wrong. Once the switch is done, the gain and offset calibration has to be redone as well, or the range will be right and the numbers will still be off.

Two things to change, not one

An analog channel has three layers: what the field signal is, how it is wired to the module, and which range the module uses to interpret it. Switching between voltage and current couples the second and third. If the wiring is changed to current input but the channel setting is left alone, the module still reads the 4 to 20 mA loop on a voltage range and the value pins near positive full scale; if only the setting is changed and the wiring left alone, the value sits near zero. Both steps belong together, and the result should be read back in the program to confirm it.

Wiring: what V+ and I+ are for

A voltage signal goes to V+ and the common terminal; a current signal goes to I+ and the common terminal, with a sampling resistor inside or outside the module turning the current into a voltage. A two-wire transmitter needs an external DC 24 V supply in series, so the loop carries both power and signal, and getting the order wrong means no sensible reading. A four-wire transmitter brings its own supply and feeds the module from two signal wires. The screen is normally earthed at the module end only, and signal cables are run in a separate duct from power cables.

Channel setting: telling the module which range to use

The channel mode lives in the module's buffer memory, written with TO and read back with FROM. On the FX2N-4AD, for example, mode 0 is voltage −10 to +10 V, mode 1 is current 4 to 20 mA, mode 2 is current −20 to +20 mA and mode 3 stops the channel. Other models offer different ranges under different numbers, so write what the manual for that module specifies. Channels with nothing wired to them are best stopped, so that an unconnected channel drifting about is not mistaken for a signal.

Converting digital values into engineering units

The digital value at full scale differs between models: 12-bit modules commonly sit around −2000 to 2000 and 16-bit modules around −32000 to 32000. The conversion is a straight proportion, and the engineering value then has its offset removed and its gain applied before it becomes the final reading.

D = (Vin ÷ Vfs) × Dfs

The live zero of 4 to 20 mA, and wire-break detection

A 4 to 20 mA loop uses 4 mA as its zero, so current is always flowing while the loop is healthy; a reading below the digital value that corresponds to 4 mA means the loop is broken, the transmitter has lost its supply or a terminal has come loose, which makes a wire-break alarm almost free. A 0 to 20 mA signal has no such convenience: zero may be a genuine zero or a broken loop, and telling them apart relies on process knowledge or extra detection. This difference is worth settling when the transmitter is chosen, because retrofitting it later is expensive.

Voltage and current inputs compared

Input typeCommon field signalWiringChannel setting to makeBehaviour on wire breakWhere it goes wrong
Voltage −10 to +10 VDisplacement, tension sensorsSignal to V+, common to VI−Select voltage range and calibrateReading drops towards zeroMixed up with a current range
Voltage 0 to +10 VPotentiometers, linear output cardsSame, watch the polarityConfirm the model supports this rangeReading drops to 0No protection for the negative direction
Voltage 0 to +5 VOlder transmitters, card outputsSameIf unsupported, change model or convert externallyReading drops to 0Scaled as 0 to 10 V, reading halved
Voltage 1 to +5 VSome pressure sensorsSameSubtract the 1 V offset at zeroReading below the 1 V valueLive zero ignored, whole span offset
Current 4 to 20 mA, two-wirePressure, level, temperature transmittersDC 24 V in series, signal to I+Select current range and calibrateReading falls below 4 mAPower and signal sharing one screen, crosstalk
Current 4 to 20 mA, four-wireAnalysers, weigh indicatorsInstrument self-powered, two wires to I+Select current range and calibrateReading falls below 4 mATwo-wire and four-wire wiring confused
Current 0 to 20 mAActuator position feedbackSignal to I+Select current rangeReading falls to 0, real zero indistinguishableUsing zero as a wire-break test
Current ±20 mABidirectional flow and force signalsSignal to I+, watch the commonSelect the bipolar current rangeReading falls to 0Mixed up with 4 to 20 mA
External sampling resistorOnly a voltage channel availableShunt resistor converts current to voltageScale and calibrate as a voltage rangeOpen resistor reads full scaleResistor tolerance and dissipation ignored
Channel stoppedChannels not yet wiredNot wiredSet to stop so it takes no part in the scanNot applicableAn empty channel drifting, taken as a signal

Notes

Switching between voltage and current is not daily work; it happens once, when a machine is modified or a transmitter replaced, so the procedure is worth writing out in full: stop the machine, isolate and prove dead, rewire, check the terminals, write the channel setting, read it back, inject two known points to calibrate, and finally run the process and watch the stability. The calibration source has to cover both ends of the range, because a single-point check will not reveal a gain error.

References

The range, resolution and accuracy of an analog channel follow GB/T 15969.2 and the equivalent international standard IEC 61131-2; immunity requirements for measurement and control equipment in its electromagnetic environment follow GB/T 18268.1 and IEC 61326-1; connection, screening and earthing of analog signal circuits follow GB 5226.1 and IEC 60204-1. Channel mode numbers and available ranges are as given in the Mitsubishi manual for the module concerned.

Points to watch

⚠️ Three common traps:
(1) Changing the wiring but not the channel setting, so the module still reads a 4 to 20 mA signal on a voltage range and the value sits at full scale while the transmitter gets the blame;
(2) Sharing one screen between supply and signal on a two-wire transmitter, so the supply current drops a voltage along the signal pair and the reading runs low and moves with the load;
(3) Skipping the recalibration after a range change, leaving the old gain and offset in place so the span is right but every value is proportionally out.

Do all five steps every time — wire, set, read back, calibrate, verify — and keep the record. Make sure the range agrees in three places: the drawing, the program comment and the module setting. Rewiring calls for a stopped machine, isolation and a lock-off; on a two-wire loop, check first that losing the transmitter supply cannot trigger a false alarm or a trip.