The parameters on a positioning module fall into three groups: one for speed, one for acceleration and deceleration, and one for position. Maximum speed sets the height of the trapezoid, the acceleration and deceleration times set the slope of the two ramps, and the target position sets the whole area. They pull on each other, so changing one usually means looking back at the other two. The two things most often got wrong are not realising that speed is in pulses per second rather than millimetres per second, and reading the acceleration time as the length of the whole ramp.
Speed is expressed in output pulses per second, and the link to mechanical travel runs through the screw lead, the reduction ratio and the pulses per motor revolution. The acceleration time is defined as the time taken to go from standstill to maximum speed; it is not the duration of the whole move, nor the horizontal length of the ramp. With those two quantities settled, the acceleration follows, and so does the number of pulses consumed by the ramp.
The usual range runs from a few tens to a few hundred milliseconds. Set it short and the mechanism takes a shock, steps can be lost and the drive may report an overcurrent; set it long and the cycle time grows, which hurts output on machines that shuttle between several positions. The sensible approach is to derive the time from the acceleration the mechanism and load will tolerate, rather than picking a number first and tuning it afterwards. If the target travel is so short that both ramps cannot fit, the module lowers the maximum speed automatically and the profile becomes triangular; the actual speed then never reaches the setpoint, and that is not a sign that the parameter failed to write.
Positions are expressed in position units, and the pulse unit multiplier sets how many position units one pulse represents: with a multiplier of 1 a pulse counts as one unit, with 10 it counts as 0.1 unit. Get the multiplier wrong by one decade and every move is ten times out, and the error is often hidden by backlash and coupling slack until a batch of parts comes out of tolerance. Several target positions sit one after another in the parameter area, each of them able to carry its own speed for two-speed operation.
Once a set of parameters is in hand, check it: convert the total travel into pulses, work out how many pulses each ramp consumes, and if the two together exceed the total the move will really be triangular. Then the positioning time is the acceleration time plus the constant-speed length divided by maximum speed plus the deceleration time. If the resulting cycle time is too long, the order of adjustment is normally to see how much headroom the maximum speed still has, then whether the acceleration time can come down, and only then the mechanical side. Reversing that order usually means endless fiddling on the electrical side.
Parameters are written into the module's buffer memory with TO, and the start bit is set afterwards. Most modules do not allow speed or position parameters to be changed while the axis is running: the write is either ignored, or takes effect only on the next positioning move, and it may raise a positioning error. The correct sequence is to stop the axis, wait for the positioning-complete signal, confirm the status bit that allows modification, write the parameters, read them back to check, and then start. Keep the start command and the parameter-enable step separate rather than on one button.
| Parameter | Unit | Typical setting | Relation to speed and ramps | What it looks like when wrong |
|---|---|---|---|---|
| Maximum speed | Pulses per second | By machine capability, commonly a few thousand to over a hundred thousand | Sets the trapezoid height and the ramp slope | Too high loses steps, too low misses the cycle time |
| Acceleration/deceleration time | Milliseconds | Commonly tens to a few hundred | Slope equals speed divided by time | Too short shocks and trips on overcurrent, too long slows the cycle |
| Target position | Position units | Converted from the travel | Sets total pulses and the profile shape | Mismatched with the multiplier, travel out by a whole factor |
| Pulse unit multiplier | 1, 10, 100 or 1000 | Usually 1 or 10 | Position units represented by one pulse | Ten times out, batch rejects |
| Creep speed | Pulses per second | Usually a few hundred or less | Makes the low-speed ramp shallower | Too high, poor repeatability at the home position |
| Position-point speed | Pulses per second | Not above maximum speed | Set individually per position | Exceeding maximum speed gets clamped |
| Positioning-complete range | Position units | By accuracy, commonly tens or less | Governs when the complete signal appears | Too wide loses accuracy, too narrow will not settle |
| Pulse output form | Pulse plus direction, dual pulse, etc. | Matched to the drive | Does not affect speed or slope | Mismatched with the drive, motor still or reversed |
| Ramp profile | Trapezoidal or polynomial | By machine rigidity | Curve shape changes the real ramp length | Trapezoidal on a rigid machine gives visible shock |
| Rotation direction | Forward or reverse | Matched to assembly | Does not affect speed or slope | Reversed, runs into the hard limit |
For commissioning, work at one position repeatedly and settle maximum speed, ramp time and multiplier first, then look at the other positions. Change one parameter at a time and record the actual positioning time and how the axis arrives; change several at once and you can no longer tell which one did the work. Wire up and prove both the soft and the hard limits during commissioning rather than adding them after the parameters are tuned.
Electrical requirements for positioning control and power drive systems follow GB 5226.1 and the equivalent international standard IEC 60204-1; EMC requirements for adjustable-speed electrical power drive systems are given in GB/T 12668.3 and IEC 61800-3; general requirements for programmable controllers and their motion control functions are given in GB/T 15969.2 and IEC 61131-2, with the semantics of programming and motion function blocks in GB/T 15969.3 and IEC 61131-3; graphical symbols and terminal designations follow GB/T 4728. Parameter numbers, units and maximum values are as given in the manual for the FX3U-1PG.
After the first setting, run the axis empty at low speed to confirm direction, travel and limits, then bring it up to working speed. Before commissioning, confirm that the emergency stop, the hard limits and the soft limits can each stop the motion on their own, and write any change to speed or ramp parameters only with the machine stopped, reading them back to verify.