Around VFDs, servo drives and contactors the inside of a cabinet is electrically the dirtiest place in the plant: their power cables both emit interference and pick it up. Run the PLC supply and signal cables tight alongside them and the symptoms range from jumping analog readings and the occasional dropped station to inputs that operate when nothing touched them. Separate routing is not superstition; it is a measure aimed at a specific coupling path.
Interference does not appear in a conductor from nowhere; it needs a coupling path. The faster the current in a power cable changes, that is, the steeper the rise and fall of voltage and current, the stronger the field around it. The nearby PLC supply and signal cables sit inside that field and have an interference voltage induced in them. Grasping the idea of a path explains why separate routing, shorter parallel runs and screening all help: each of them weakens that path.
Conducted coupling travels along a shared supply circuit, so interference reaches the PLC supply terminals directly through the conductors. Capacitive coupling works through the stray capacitance between two conductors, which hands the interference across as the voltage changes. Inductive coupling induces a voltage in a neighbouring loop as the current changes. Each needs a different answer: conducted coupling yields to filters and an isolation transformer, capacitive and inductive coupling yield to greater separation, shorter parallel runs, screening and proper earthing. Doing only one of them usually knocks the interference down by a fraction, not away.
A VFD outputs a high-frequency switched pulse voltage with steep edges, and there is significant stray capacitance between the output cable and earth, producing a high-frequency leakage current. That cable is both a strong source and an effective way of passing interference to others through the earth path. So it is normally treated on its own: screened cable, the screen bonded to earth over a large area at both ends, a larger separation from signal cables, and an output reactor or a dv/dt filter where needed.
The basics are separate ducts, separate layers and separate sides: motor power and signal cables run in different ducts, or in the same duct divided by a metal barrier. Where the two must cross, cross as near to right angles as possible rather than in a long parallel run. Where they must run parallel, keep the separation adequate, and widen it with voltage level and current. Inside the cabinet, keep strong-current and low-level areas apart, placing the power supply and VFDs away from the PLC and transmitters, so sources and sensitive equipment are physically separated.
A screen works by capturing interference and carrying it away, which requires the screen to be properly earthed. Signal-cable screens are normally earthed at one end, at the control system side, so that earthing at both ends does not create an earth loop that injects interference instead. Bond the screen over a large area at low impedance, using a clamped screen gland rather than a long thin "pigtail". Power-cable screens are normally earthed at both ends. The earth system should be equipotential, so that no potential difference exists between separate earthing points.
| Practice | Coupling route addressed | Expected effect | Points to watch |
|---|---|---|---|
| Separate ducts for power and signal | Capacitive and inductive | Marked reduction in induced interference | Separation set by voltage and current |
| Metal barrier inside one duct | Capacitive and inductive | Clear improvement over mixed routing | Barrier must be metal and earthed |
| Right-angle crossings | Inductive | Shorter coupling length | Avoid long parallel runs |
| Separation on parallel runs | Capacitive and inductive | More distance, less interference | Increase with voltage level |
| Single-ended signal screen earth | Interference via earth loops | No earth loop formed | Earth at the control system side |
| Large-area screen bonding | High-frequency coupling | Low impedance at high frequency | No thin wire substitute for bonding |
| Screened VFD output cable | Radiated and conducted emission | Lower emission level | Screen earthed at both ends |
| Input filter on the VFD | Conducted | Lower conducted emission | Mount close to the drive |
| Output reactor on the VFD | Conducted and radiated | Lower high-frequency current | Match to the drive rating |
| Strong/low-level zoning in the cabinet | All routes | Distance created at the root | No shared compartment |
Interference work starts at three places: the source, the path and the victim. First cut emission at the source with filters, reactors and screened cable, then cut the path by separating routing, keeping distance and earthing screens, and finally raise the immunity of the victim with supply filtering, signal filtering and opto-isolation. Treating only one of the three usually leaves a residue, which is why sites re-work the same problem repeatedly. On retrofit projects watch duct utilisation: pushing new power cables into an existing signal duct is the commonest reason a machine that ran fine suddenly becomes unstable.
Electrical connection, protection and earthing inside a control cabinet follow GB 5226.1 and IEC 60204-1. Electromagnetic compatibility requirements for adjustable-speed electrical drive systems follow the GB/T 12668 series and IEC 61800-3. Cable selection, screening practice and separation distances specific to a machine are as stated in the manufacturer's installation rules; the items listed here illustrate the approach.
Any routing change inside a cabinet requires the machine to be stopped, the supply isolated, proved dead and locked off; after earthing work, measure the continuity of the earth connections to confirm equipotential bonding.