For multi-Mitsubishi-PLC networks there are three common routes: FX5U / iQ-R controllers use their built-in Ethernet port to run CC-Link IE Field Basic, FX3U systems add a CC-Link master module to run classic CC-Link, or any model can be polled over Ethernet with the SLMP protocol. The sections below walk through choosing the network, configuring the stations and organising the refresh areas.
| Method | Suitable models | Medium | Character |
|---|---|---|---|
| CC-Link IE Field Basic | FX5U, iQ-R built-in Ethernet | Ordinary Ethernet cable | Cyclic communication, no special hardware, fine for small node counts |
| CC-Link (fieldbus) | FX3U with FX3U-16CCL-M etc. | Dedicated twisted pair | Good noise immunity, tidy station expansion, common on older lines |
| Ethernet SLMP / MC protocol | Nearly all series | Ethernet cable | Master polling with program-driven exchange, flexible but costs code |
For new projects prefer CC-Link IE Field Basic: the cable is cheap, configuration is simple and cyclic refreshing needs no communication program. Keep CC-Link on legacy lines; for a one- or two-machine data roll-up, SLMP polling is the cheapest route.
Step by step: ① Navigation window → Parameter → FX5UCPU → Module Parameter → Ethernet; ② in the basic settings select "CC-Link IE Field Basic" and set this station as the control station (master) or a normal station; ③ set each slave's station number and refresh device start (e.g. W0, W100, one block per station); ④ configure every slave PLC the same way as a normal station with the same network number; ⑤ download the parameters to each PLC and restart.
Key points: all stations must share the same network number, and the refresh device ranges must not overlap. Give the master W0~W1F to station 1's inputs, draw up a refresh table and paste it into the program so that who writes and who reads is obvious at a glance.
The master module occupies X/Y points and buffer memory, and the station information is written into the parameters (G0~G2 and so on): the total number of stations and the station count each slave occupies (1, 2 or 4 stations, which decides the 32/64-point refresh volume). The remote inputs RX and remote outputs RY are mapped into local devices via FROM/TO instructions or auto refresh. The line uses DA-DB twisted shielded pair with terminating resistors at both ends — a missing terminating resistor is the most common cause of "every station offline".
| Station | Refresh devices (inputs) | Refresh devices (outputs) | Suggested content |
|---|---|---|---|
| Master | W0~W1F | W100~W11F | Command words the master sends out |
| Station 1 | W20~W3F | W120~W13F | Status, production count, alarm word |
| Station 2 | W40~W5F | W140~W15F | Same as above |
| Station 3 | W60~W7F | W160~W17F | Same as above |
| Reserved | W80~W9F | W180~W19F | Keep one or two stations for expansion |
Give every station a heartbeat word (say W20 incrementing continuously); if the master sees the heartbeat stop, it declares that station offline. This is far more reliable than noticing "the data suddenly went all zeros".
The master sends soft-element read/write requests to each station's IP in turn using one-shot instructions or a communication library, polling station by station; each exchange gets a timeout with retries, and N consecutive timeouts declares the station offline. The advantage is that an ordinary switch is enough and routing across segments works; the drawback is that real-time behaviour degrades as the station count grows, so it does not suit tightly synchronised interlocks.
| Item | What to verify | Common mistake |
|---|---|---|
| Network / station numbers | Unique and consistent across the network | Two controllers both set as control station, network never starts |
| IP addresses | Same subnet, no conflicts | Clashing with the plant network and being routed away |
| Refresh devices | No overlap between stations | Overlapping ranges overwrite each other's data |
| Cabling | Cat5e or better; CC-Link terminating resistors fitted | Missing terminators, all stations offline |
| Heartbeat monitoring | Heartbeat word per station + master timeout detection | No heartbeat, a dropped station freezes stale data unnoticed |
| Shield earthing | Shield earthed at one end | VFD noise causes intermittent comms errors |
| Download order | Slaves first, master last | Master starts first, reports slaves offline, hardware blamed in error |
| Documentation | Refresh table and IP list archived in the panel | Six months later nobody remembers which block belongs to whom |
At its heart, networking means "sharing a region of devices both sides agree on": whatever the method, machine A's data is periodically moved to an agreed address and machine B reads from that address. Get the refresh table right and changing the protocol is just changing the vehicle that does the moving.
Configuration follows the Mitsubishi MELSEC iQ-F FX5 User's Manual (CC-Link IE Field Basic) and the CC-Link System Master Module User's Manual; electrical installation and earthing follow GB 5226.1 (equivalent to IEC 60204-1). Station and refresh limits follow the current revision of each manual.
During commissioning, get every station's heartbeat and offline alarm working before linking any actions; a printed network diagram and refresh table taped inside the panel is the most valuable sheet of paper for later maintenance.