The watch table shows "???", sticks at zero, or disagrees with the machine — the search covers three grounds: the variable itself (name, scope, address), the access mode (symbol/absolute, optimised blocks), and communication and refresh. Match the items below and ten minutes settles it.
| Symptom | Points to | First check |
|---|---|---|
| "???" / format error | Name/path does not exist, type unrecognised | Variable name and scope |
| Stuck at 0 / OFF, never moves | Wrong address, logic not driving, comms down | Cross-reference + online status |
| Value "wrong" | Type misinterpreted, scaling wrong, write/read areas mixed | Data type and scaling |
① Spelling/case: variable names are case-sensitive or auto-completed — hand-typing errs, so pick from the variable browser instead; ② local versus global: FB/FC-local variables are invisible to an external watch table — monitor locals inside the block's own monitor view; ③ same-name shadowing: two scopes holding the same name, the table resolving to the other one; ④ deleted/renamed variables: after a project revision the table keeps stale names and shows "???". Any "???" starts at the symbol table: does the variable exist, spelled identically?
| Problem | Symptom | Fix |
|---|---|---|
| Absolute address mistyped (D100 as D10) | Zero or random junk | Verify the address from the symbol table |
| Optimised-block access (S7-1500) | Absolute-address monitoring fails | Monitor optimised blocks by symbol; handle non-optimised data separately |
| Type misread (word read as REAL) | Astronomical values | Select the correct data type in the table |
| Byte order / high-low words | Double-word halves swapped | Confirm the platform's and source's word order |
| Combined addressing mistyped | Bits read skewed | Verify K4Y0-style starts |
The highest-frequency "wrong value" is type misinterpretation: the same D reads 12345 as INT, an astronomer's number as REAL, something else as BCD — first establish "what type actually lives at this address", then set the monitor's type.
① Monitor connection not established: confirm "online" in the title/status bar — a dropped link freezes values at their last state, easily misread as "data not moving"; ② refresh period: watch tables refresh on a cycle set somewhere — too slow and fast changes blur (not unreadable, just unseen); ③ read limits: some platforms cap monitor connections/variable counts — beyond them variables stop refreshing; ④ simulator versus machine: the simulator monitors simulated data — connected to the wrong environment you study fiction for an hour.
With type and comms excluded, the data itself is wrong in the logic: ① multiple writers to one address (the data version of a double coil) — cross-reference the writers and find the overwriter; ② wrong scaling factor — display × factor off by a fixed multiple; ③ the variable is an intermediate being flushed by initialisation — check the initialisation trigger; ④ retained data reinterpreted under a changed structure — restore or re-initialise. Use "writer watching" (monitor the address while listing every write site) to catch the overwriter.
| Step | Action | Pass → |
|---|---|---|
| 1 | Confirm online status (not simulator, not dropped) | Next |
| 2 | Variable picked from the browser, not hand-typed | Next |
| 3 | Type and address verified from the symbol table | Next |
| 4 | Cross-reference lists every write site | Next |
| 5 | Watch the write sites, catch the overwriter | Located |
| 6 | Still odd → check scaling and structure interpretation | Located |
Ninety percent of watch-table trouble lives in the "correspondence between table and data": is the name right (scope), the address right, the type interpretation right, the link alive (online/simulator)? Fix the correspondence before suspecting logic — data overwriting (double writes) is real, but it is not the first suspect.
Watch/monitor-table functions and limits follow the platform manuals (GX Works device monitor, TIA watch tables, CODESYS watch views); optimised-block and symbol-access rules follow the storage and compilation documentation; type interpretation and byte order follow the platform documents and the data-source protocol.
The first step of every watch-table hunt is one glance at the online status bar — three seconds eliminating a whole class of problems.