How do you troubleshoot a watch table that shows no value or incorrect values?

The watch table shows "???", sticks at zero, or disagrees with the machine — the search covers three grounds: the variable itself (name, scope, address), the access mode (symbol/absolute, optimised blocks), and communication and refresh. Match the items below and ten minutes settles it.

1. First split the three symptoms

SymptomPoints toFirst check
"???" / format errorName/path does not exist, type unrecognisedVariable name and scope
Stuck at 0 / OFF, never movesWrong address, logic not driving, comms downCross-reference + online status
Value "wrong"Type misinterpreted, scaling wrong, write/read areas mixedData type and scaling

2. The name and scope layer

① Spelling/case: variable names are case-sensitive or auto-completed — hand-typing errs, so pick from the variable browser instead; ② local versus global: FB/FC-local variables are invisible to an external watch table — monitor locals inside the block's own monitor view; ③ same-name shadowing: two scopes holding the same name, the table resolving to the other one; ④ deleted/renamed variables: after a project revision the table keeps stale names and shows "???". Any "???" starts at the symbol table: does the variable exist, spelled identically?

3. The address and access-mode layer

ProblemSymptomFix
Absolute address mistyped (D100 as D10)Zero or random junkVerify the address from the symbol table
Optimised-block access (S7-1500)Absolute-address monitoring failsMonitor optimised blocks by symbol; handle non-optimised data separately
Type misread (word read as REAL)Astronomical valuesSelect the correct data type in the table
Byte order / high-low wordsDouble-word halves swappedConfirm the platform's and source's word order
Combined addressing mistypedBits read skewedVerify K4Y0-style starts

The highest-frequency "wrong value" is type misinterpretation: the same D reads 12345 as INT, an astronomer's number as REAL, something else as BCD — first establish "what type actually lives at this address", then set the monitor's type.

4. The communication and refresh layer

① Monitor connection not established: confirm "online" in the title/status bar — a dropped link freezes values at their last state, easily misread as "data not moving"; ② refresh period: watch tables refresh on a cycle set somewhere — too slow and fast changes blur (not unreadable, just unseen); ③ read limits: some platforms cap monitor connections/variable counts — beyond them variables stop refreshing; ④ simulator versus machine: the simulator monitors simulated data — connected to the wrong environment you study fiction for an hour.

5. The logic layer for "values wrong"

With type and comms excluded, the data itself is wrong in the logic: ① multiple writers to one address (the data version of a double coil) — cross-reference the writers and find the overwriter; ② wrong scaling factor — display × factor off by a fixed multiple; ③ the variable is an intermediate being flushed by initialisation — check the initialisation trigger; ④ retained data reinterpreted under a changed structure — restore or re-initialise. Use "writer watching" (monitor the address while listing every write site) to catch the overwriter.

6. The flow to walk

StepActionPass →
1Confirm online status (not simulator, not dropped)Next
2Variable picked from the browser, not hand-typedNext
3Type and address verified from the symbol tableNext
4Cross-reference lists every write siteNext
5Watch the write sites, catch the overwriterLocated
6Still odd → check scaling and structure interpretationLocated

7. Notes

Ninety percent of watch-table trouble lives in the "correspondence between table and data": is the name right (scope), the address right, the type interpretation right, the link alive (online/simulator)? Fix the correspondence before suspecting logic — data overwriting (double writes) is real, but it is not the first suspect.

8. References

Watch/monitor-table functions and limits follow the platform manuals (GX Works device monitor, TIA watch tables, CODESYS watch views); optimised-block and symbol-access rules follow the storage and compilation documentation; type interpretation and byte order follow the platform documents and the data-source protocol.

9. Cautions

⚠️ Three traps to avoid:
① A hand-typed variable name misspelled shows "???" and comms gets blamed;
② Reading BCD as INT — the longer you look, the less it makes sense;
③ A dropped link freezing values, misread as "process data not moving" — the process gets investigated for nothing.

The first step of every watch-table hunt is one glance at the online status bar — three seconds eliminating a whole class of problems.