Which situations call for a reset-dominant function block?

Reset-dominant: when the set and reset signals arrive together, the output goes OFF — reset wins. That "on conflict, listen to the stop" temperament is exactly what safety needs: when start and stop collide, the machine must stop. The sections below map the right applications, contrast set-dominant, and show how to write it.

1. The two dominants, distinguished

TypeWhen set and reset are both activeTemperamentSuitable duty
Reset-dominantOutput OFF (reset wins)Conflict means stopDrives, safety-related outputs
Set-dominantOutput ON (set wins)Conflict means motionRarely for mechanisms; mostly "first event" recording

Beware the naming trap that vendors invert: in IEC 61131-3 the SR block (set-dominant) lets set win, the RS block (reset-dominant) lets reset win; in Mitsubishi-style sequential SET/RST writing, the RST written last wins = reset-dominant. Verify with the truth table, never memorise abbreviations.

2. Where reset-dominant is mandatory

① Motor/drive start-stop: when start and stop (including E-stop feedback) coincide, the motor must stop — stop dominance is a basic principle of GB 5226.1; ② clamp/unclamp logic: clashing clamp and unclamp commands resolve to unclamped (a dropped part can be picked up, a pinched hand cannot be undone); ③ line-start permission: a start request colliding with any unready safety condition yields no start; ④ alarm latching: while the alarm source persists, the reset key does nothing — alarm beats reset, preventing a "reset while sick"; ⑤ valve interlocks: clashing open/close commands resolve to the safe position (usually closed).

3. The truth table: the conflict row is the soul

Set SReset RReset-dominant outputSet-dominant output
00HoldsHolds
1011
0100
1101

When reviewing any start/stop logic, look only at the fourth row: with S = R = 1, what is the output? For a power output it must be 0 — a 1 goes straight back to the drawing board.

4. Writing reset-dominant in ladder

The plainest form is putting RST after SET:

LD start condition → SET M10; LD stop condition → RST M10 (RST last wins the conflict)

On function-block platforms use the RS block (reset-dominant) with S1 on start and R on stop. The sturdier pattern is "reset condition wired into the output branch": OUT Y0 = set-memory AND NOT stop-condition — the stop does not participate in the memory at all but presses on the branch continuously, so even a corrupted memory cannot hold the output against a stop. This double-insurance pattern is recommended for all power outputs.

5. Where set-dominant legitimately belongs

Set-dominant suits "recording that it happened": ① first-out alarms — among simultaneous alarms, lock the first, using set-dominant with mutual exclusion; ② event flags — when clashing with later clear signals, keep the "it occurred" fact. The common trait: the output never drives a mechanism directly — set-dominant outputs only feed records and indications. Hold that line and the two dominants never swap duties.

6. Common errors

SymptomCauseFix
Motor keeps turning during E-stopStart/stop written set-dominant (or E-stop only inside the SET branch)Reset-dominant + E-stop wired into the output branch
Alarm "revives" after resetSource still present, reset cleared the flag anywayReset invalid while the alarm persists
Behaviour flips after a platform changeSR/RS naming difference, truth table never checkedRe-verify the fourth row
Output flickers at the conflict instantSET and RST in different networks, scan-order sensitiveHandle the conflict in one network / one block

7. Notes

Choosing a dominant is choosing who absorbs the conflict risk: for power mechanisms the risk must go to the machine (stop), hence reset-dominant; for event records the risk is "losing detail", hence set-dominant. Remember who owns the risk and the choice stops being memorisation.

8. References

Stop dominance and stop-function independence follow GB 5226.1 / IEC 60204-1; SR/RS block definitions follow IEC 61131-3; verification of safety-related logic follows GB/T 16855.1 (ISO 13849-1).

9. Cautions

⚠️ Three traps to avoid:
① Memorising abbreviations instead of checking the truth table — after a platform change SR/RS invert and the power output starts on conflict;
② E-stop participating only in the set-memory rather than the output branch — a corrupted memory defeats the E-stop;
③ Alarm reset without "reset invalid while source present" — resetting while sick invites the second incident.

For power outputs always double-insure: reset-dominant memory + stop condition in the output branch. At review, ask one question: "start and E-stop together — what is the output?" An answer of 1, or no answer, sends it back.