In the compact tier (20~200 points, logic-dominated, a little analog and one or two positioning axes), the gap between domestic (Inovance, Xinje, Delta and peers) and imported (Mitsubishi, OMRON, Siemens) PLCs has moved from "can it do the job" to "how pleasant is it to do the job". The real gaps concentrate in three places: high-end instruction and motion capability, software engineering experience, and long-term reputation and ecosystem. Laying the three out settles most selection debates. The comparison below goes item by item.
| Aspect | Domestic mainstream | Imported mainstream | Verdict |
|---|---|---|---|
| Discrete logic | Fully capable | Fully capable | No practical difference |
| Analog handling | Good enough; resolution and accuracy up to spec | Up to spec, finer filtering and diagnostics | Very small |
| Positioning | Pulse positioning mature; EtherCAT bus now widespread | Bus ecosystem more mature | Pulse parity; bus ecosystem slightly behind |
| Protocols | Modbus everywhere, own Ethernet protocols | Large proprietary-protocol ecosystem, many third-party device drivers | Third-party ecosystem still behind |
| Programming software | Fast progress, main-line features covered | More mature engineering, simulation and library management | Experience gap visible |
| Reliability reputation | Much improved over the last decade, unit variance exists | Long stable reputation | Narrowing |
| Price and service | Roughly 1/2~2/3 of imported; fast, flexible support | Pricier, channel-driven service | Domestic advantage |
① High-end motion control: multi-axis interpolation and electronic-cam maturity and debugging literature still lead on the imported side, though that tier usually outgrows compact hardware anyway; ② software engineering: library management, version comparison, simulation fidelity — the imported tools are more mature, and the gap shows on large projects; ③ ecosystem and literature: third-party tutorials, forum cases and experienced engineers — imported brands carry a decade of stock advantage: recruiting, searching, spare parts all flow easier.
Domestic strengths are equally concrete: fast response (support engineers reachable directly), flexible customisation (protocols and firmware adjusted to demand), lower price, short supply cycles. For retrofit and special-purpose machine projects these often outweigh "ecosystem".
| Project type | Lean towards | Reason |
|---|---|---|
| Standalone machines, special-purpose equipment | Domestic | Logic + analog + 1~2 axes; price and response first |
| Line retrofits, phased builds | Follow existing stock | Consistency with the installed base eases maintenance |
| Multi-axis sync, complex motion | Imported or domestic mid/large | Motion ecosystem and literature depth |
| Customer-specified brand | Specified | Acceptance and service follow the customer's system |
| Cost-sensitive, volume machines | Domestic | Significant batch price gap, stable supply |
Moving from imported to domestic (or back) carries three hidden bills: ① learning cost: device systems and software habits take a week or two; ② migration cost: existing programs are rewritten, not translated — it is a rework; ③ spares system: panel spares, maintenance tools and service contracts follow the brand. So "one machine switches" is common, "a whole plant switches" is rare — the installed base determines inertia, and that is the imported brands' home ground.
Keep these in mind when writing proposals: ① some advanced instruction functions (special function blocks, library standards) are incomplete; ② simulation diverges more from real hardware — leave real-machine time for critical logic; ③ English literature is thin — evaluate for export projects; ④ lifecycle management (discontinuation notices) on some models is less formal than the big houses — ask about discontinuation policy before a volume order and you will not be caught out.
For the compact tier the verdict can be blunt: on control function, domestic hardware is good enough and getting steadier; the gaps are in software experience and ecosystem depth. Choose by project arithmetic — function sufficient, budget tight, response valued → domestic; ecosystem heavy, installed base large, customer specified → imported. The "domestic is not trustworthy" argument no longer holds in this tier.
The comparison draws on public selection guides and catalogues of the manufacturers named, plus engineering practice; specific model ratings follow the catalogues; control-function design must satisfy GB 5226.1 / IEC 60204-1 regardless of brand.
Whatever the brand, solid drawings, commented programs and a real spares list are what keep a machine maintainable — the brand is a tool; discipline is the asset.