When a program refuses to download, nine times out of ten the cause sits in the communication link, the transfer setup or a protection mechanism — an actually broken CPU is rare. Do not thrash: follow the order cable → driver → transfer setup → PLC state → protection → project and check one thing per layer.
| Layer | Check | How to judge |
|---|---|---|
| Physical | Ethernet/USB plugged in, switch port lit, PLC power LED on | Swap cable, swap port |
| Network | PC IP in the same subnet as the PLC, no conflict | Ping the PLC's IP from cmd |
| Driver | USB driver installed, COM port present in Device Manager with no exclamation mark | Reinstall the GX Works bundled driver |
| Setup | Transfer setup matches the actual connection | "Communication test" gives a direct verdict |
| PLC side | PLC in a writable state, no write-inhibit setting | Check the RUN/STOP switch and LEDs |
| Protection | No file password / key word protection | Connecting reports "password protected" |
| Project | Compiled, PLC type matches the actual model | Convert (F4) and verify the model |
Most problems surface at the "communication test" step: only if the test passes and the download still fails should you look at PLC state and protection.
① IP not reachable: factory PLC IPs are often 192.168.3.39-style, so the PC NIC must be on the same subnet; ② routing across subnets missing or via the wrong NIC (a laptop on WiFi plus the PLC cable — routing takes the WiFi): unplugging WiFi is the direct fix; ③ FX5U needs the right "Current Connection Target" (Ethernet direct or a specified IP); ④ the switch has port isolation or a VLAN separating the two ends.
Ping OK but the software cannot connect: the peer port/protocol settings were changed, or the connection target is set wrong (USB direct instead of Ethernet).
① Driver missing or a generic serial driver installed — Device Manager shows "unknown device" or a yellow mark; reinstall the dedicated driver from the GX Works package; ② the COM number changed: after moving USB ports the number shifts and the transfer setup must follow; ③ the "USB cable" is a charge-only cable without data lines — use a proper data cable; ④ the first connection triggers new-hardware detection — wait for the driver to finish before testing.
| Cause | Symptom | Action |
|---|---|---|
| File password on the PLC | "PLC file protected / key word required" | Get the password from the owner, log in, then download |
| Model mismatch | "Different PLC type / cannot write" | Project → Change PLC Type to the real model |
| Not compiled | "Program contains unconverted data" | Convert all programs (F4 or batch) |
| PLC fault | ERR lamp lit, error code points to memory | Handle per the manual; initialise if needed and re-download |
Record password protection carefully: when taking over equipment, confirm up front whether a password exists, rather than discovering it during a breakdown.
In the download dialog tick "program + parameters"; do not casually tick device memory — it would overwrite field calibration and recipes with the old data on the PC. A parameter write asks for a PLC reset/restart; on a production line confirm the stop window first. After the download, check PLC diagnostics for alarms before letting the machine move.
Downloading over a router/VPN: watch MTU and latency timeouts — raise the software timeout and download in batches (parameters first, program next). Large programs over 4G remote modules break easily; switch to a resumable path or hang a commissioning laptop next to the gateway. A dropped wireless transfer leaves a half-written program — you must re-download completely and verify; never assume only the last bit was missing.
Downloading is "open a session → verify model and project → transfer in blocks → reset to take effect". Each break point has its own error text: cannot connect → link layer; password → protection; model → project. Matching the message to the layer beats trying everything in random order.
Transfer setup and download follow the Mitsubishi GX Works3 Operating Manual (connection target, PLC write); USB driver installation is in the manual appendix; password protection is in the MELSEC iQ-F FX5 User's Manual (Security/Password). Remote maintenance security follows corporate IT policy.
Remember the order: communication test first, then protection and model, hardware last. After every download, read the program back once to confirm the live program matches the project.