What steps do you follow when a Mitsubishi PLC program will not download?

When a program refuses to download, nine times out of ten the cause sits in the communication link, the transfer setup or a protection mechanism — an actually broken CPU is rare. Do not thrash: follow the order cable → driver → transfer setup → PLC state → protection → project and check one thing per layer.

1. The troubleshooting route: physical layer upward

LayerCheckHow to judge
PhysicalEthernet/USB plugged in, switch port lit, PLC power LED onSwap cable, swap port
NetworkPC IP in the same subnet as the PLC, no conflictPing the PLC's IP from cmd
DriverUSB driver installed, COM port present in Device Manager with no exclamation markReinstall the GX Works bundled driver
SetupTransfer setup matches the actual connection"Communication test" gives a direct verdict
PLC sidePLC in a writable state, no write-inhibit settingCheck the RUN/STOP switch and LEDs
ProtectionNo file password / key word protectionConnecting reports "password protected"
ProjectCompiled, PLC type matches the actual modelConvert (F4) and verify the model

Most problems surface at the "communication test" step: only if the test passes and the download still fails should you look at PLC state and protection.

2. Common causes on an Ethernet download

① IP not reachable: factory PLC IPs are often 192.168.3.39-style, so the PC NIC must be on the same subnet; ② routing across subnets missing or via the wrong NIC (a laptop on WiFi plus the PLC cable — routing takes the WiFi): unplugging WiFi is the direct fix; ③ FX5U needs the right "Current Connection Target" (Ethernet direct or a specified IP); ④ the switch has port isolation or a VLAN separating the two ends.

Ping OK but the software cannot connect: the peer port/protocol settings were changed, or the connection target is set wrong (USB direct instead of Ethernet).

3. Common causes on a USB download

① Driver missing or a generic serial driver installed — Device Manager shows "unknown device" or a yellow mark; reinstall the dedicated driver from the GX Works package; ② the COM number changed: after moving USB ports the number shifts and the transfer setup must follow; ③ the "USB cable" is a charge-only cable without data lines — use a proper data cable; ④ the first connection triggers new-hardware detection — wait for the driver to finish before testing.

4. Four causes when the link is fine but the download fails

CauseSymptomAction
File password on the PLC"PLC file protected / key word required"Get the password from the owner, log in, then download
Model mismatch"Different PLC type / cannot write"Project → Change PLC Type to the real model
Not compiled"Program contains unconverted data"Convert all programs (F4 or batch)
PLC faultERR lamp lit, error code points to memoryHandle per the manual; initialise if needed and re-download

Record password protection carefully: when taking over equipment, confirm up front whether a password exists, rather than discovering it during a breakdown.

5. Download scope and the confirmation dialog

In the download dialog tick "program + parameters"; do not casually tick device memory — it would overwrite field calibration and recipes with the old data on the PC. A parameter write asks for a PLC reset/restart; on a production line confirm the stop window first. After the download, check PLC diagnostics for alarms before letting the machine move.

6. Special cases: remote and wireless

Downloading over a router/VPN: watch MTU and latency timeouts — raise the software timeout and download in batches (parameters first, program next). Large programs over 4G remote modules break easily; switch to a resumable path or hang a commissioning laptop next to the gateway. A dropped wireless transfer leaves a half-written program — you must re-download completely and verify; never assume only the last bit was missing.

7. Notes

Downloading is "open a session → verify model and project → transfer in blocks → reset to take effect". Each break point has its own error text: cannot connect → link layer; password → protection; model → project. Matching the message to the layer beats trying everything in random order.

8. References

Transfer setup and download follow the Mitsubishi GX Works3 Operating Manual (connection target, PLC write); USB driver installation is in the manual appendix; password protection is in the MELSEC iQ-F FX5 User's Manual (Security/Password). Remote maintenance security follows corporate IT policy.

9. Cautions

⚠️ Three traps to avoid:
① Laptop WiFi still on, routing via wireless, ping fails and the PLC gets blamed;
② Ticking device memory in the download and overwriting field calibration with stale PC data;
③ After a broken wireless transfer, not re-downloading completely — the mangled program produces bizarre motion.

Remember the order: communication test first, then protection and model, hardware last. After every download, read the program back once to confirm the live program matches the project.