A CP1E model designation is really a configuration sheet: series grade, I/O count, power type and output form are all in the string. Read the naming and the catalogue selection gains a main line. The sections below decode the naming and list the seven selection checks.
| Field | Example | Meaning |
|---|---|---|
| CP1E- | CP1E | Series name (compact packaged PLC) |
| Grade letter | N / NA / E | E = economical; N adds a serial port; NA adds built-in Ethernet on top of N |
| I/O points | 20 (10/14/16/20/30/40/60) | Total inputs + outputs of the base unit |
| Power type | A / D | A = AC100~240 V supply; D = DC24 V supply |
| Output form | R / T | R = relay outputs; T = transistor outputs (N/NA types) |
| Input form | D | DC24 V inputs (general purpose) |
So CP1E-NA20DR-D reads as: NA grade with built-in Ethernet, 20 points, DC24 V supply, relay outputs, DC inputs. Note the point count is inputs plus outputs combined; a 20-point unit is typically 12 in / 8 out — check the terminal diagram in the catalogue.
The E type is cheapest, with no built-in serial port and limited expansion, right for pure-logic small machines; the N type carries an RS-232C port for text panels and inverters — choose it when no network is needed; the NA type has built-in Ethernet for host links, remote monitoring or Ethernet downloads, and the extra cost is worth it. All three grades program in CX-Programmer with the same instruction set, so program migration costs little.
| Check | What to verify | Rule of thumb |
|---|---|---|
| 1. I/O count | Count the field I/O, add 20~30% spare | Keep a few spare relay contacts and proximity inputs |
| 2. Output form | High-frequency DC-only loads → transistor; mixed, slow → relay | For frequently switched solenoids, do the relay-life maths first |
| 3. Power type | DC24 V already in the panel → D; only AC220 V → A | D can share the sensor 24 V rail, but check capacity |
| 4. Expansion | Analog, temperature, more I/O via CP1W units | Check how many expansion units the model accepts |
| 5. Communication | HMI/inverter on serial, host on Ethernet | If serial is used up, add a CP1W-CIF port |
| 6. Special functions | High-speed counting, pulse-output axes | For stepper/servo positioning count the built-in pulse outputs |
| 7. Software and spares | CX-Programmer version supports the model; local stock | Downtime-sensitive lines keep spares on site |
Relay outputs (R) are universal but mechanically short-lived: a solenoid cycling every 2 seconds makes roughly 7.8 million operations a year, far beyond relay life — that duty demands transistor outputs plus an interposing relay or a solid-state load. Conversely, for contactor coils switching infrequently at higher current, relay outputs are simpler. List the switching frequency of every output — that matters more than the point table.
CP1W expansions clip to the right of the base unit: digital (CP1W-20EDR1 etc.), analog (CP1W-AD041 / DA041 / DAQ), temperature (CP1W-TS series) can be mixed, but the total is capped per model (typically three units, fewer on E). At selection, verify "base points + expansion points + unit count" in one pass so you do not discover halfway that nothing more can be added.
| Machine scenario | Recommended model logic | Reason |
|---|---|---|
| Single panel, a few motors and valves | CP1E-E 20-point relay output, AC power | Pure logic, low speed, lowest cost |
| 3-inch text panel + inverter comms | CP1E-N 30 points | Needs the built-in serial port |
| Production counts into plant system | CP1E-NA 20~30 points | Built-in Ethernet, no comms unit needed |
| Analog temperature control + 2 stepper axes | N/NA 40 points + CP1W temperature/analog | Both expansion capacity and pulse outputs must be checked |
CP1E is positioned as a low-cost compact PLC: logic and simple communication are fine, but do not stretch it for motion control or heavy data work. The selection rhyme: spare points, frequency decides the output, communication decides the grade, verify expansion caps early.
Naming and specifications follow the OMRON CP1E Series Catalogue / Selection Guide and the CP1E Hardware User's Manual; output life, expansion caps and pulse-output ratings follow the latest catalogue; control-circuit design safety follows GB 5226.1 / IEC 60204-1.
Walk the catalogue terminal diagram point by point against the selection sheet and mark the spare points on the drawing — those two hours save half the later arguments.