Working out the supply capacity means keeping two budgets apart. The DC 5 V inside the rack is fed by the power supply module; the field DC 24 V for sensors and output loads may come from the same module or from a separate switching power supply. The two budgets have different objects but share the rated output of one supply, so they must be added item by item with a margin on top. The sections below give the accounting basis, how to take the margin, and what to do when capacity is short.
At least three branches have to be separated: the 5 V current on the backplane or base plate, which feeds the internal circuits of the CPU, I/O and communication modules; the 24 V auxiliary current, which feeds proximity switches, photoelectric sensors, interposing relay coils and pushbutton lamps; and the field load current carried independently by an external switching supply. What is being accounted for is whether the sum of the first two branches stays within the rated output of the power supply module; the third does not load the internal supply but must be checked for its own capacity and voltage drop.
The 5 V consumption of each module is given separately in the manufacturer's manual and must be added module by module: the CPU, the power supply itself, each digital module, each analog module, the communication module and each expansion base all count. Estimating from the CPU nominal figure alone is not enough; once the rack is full the actual consumption often approaches or even exceeds the rated output of a small supply.
The 24 V side is mainly external devices. Each proximity or photoelectric switch is counted at the manufacturer's nominal current, usually a few tens of milliamperes each; each interposing relay and solenoid valve coil is counted at its holding current, with the inrush at pick-up noted separately; pushbutton lamps are counted at a few to a few tens of milliamperes each. These devices are numerous and their total is often larger than the 5 V side, which is why this branch is the one most easily forgotten. The 24 V rail is also often used as the load supply for digital outputs, and that part must be calculated for the worst simultaneous combination.
The result must not be used right up to the rated value. As a working limit, about 60% to 70% of the rated output of the power supply module is usually taken, leaving the margin for temperature rise, supply fluctuation and later additions. When installed in a closed cabinet or at high ambient temperature, derate further, using the temperature curve given in the manufacturer's manual. Account also for the switch-on inrush and the worst case of simultaneous operation rather than an average load.
There are four options, in order of rising cost: move the 24 V field loads to an external switching supply to free internal capacity; refine the simultaneous-operation combination, using grouped delays to cut the instantaneous peak where necessary; fit a power supply module of larger capacity; or adopt distributed I/O or local field supply to spread the loads out. After any change, re-check the base plate current limit and the voltage drop.
| Load | Supply source | Current basis | Key point |
|---|---|---|---|
| CPU and the power module itself | Internal 5 V | As given in the manual | Add module by module, none omitted |
| Digital input module | Internal 5 V | As given in the manual | Count by module, not by point |
| Digital output module | Internal 5 V plus 24 V load | Internal 5 V plus load current | Keep the two budgets apart |
| Analog module | Internal 5 V | Manual value, larger for analog | Grows with channel count |
| Communication module | Internal 5 V | As given in the manual | Count each card separately |
| Expansion base | Internal 5 V | Sum of the modules it carries | Add to the main base total |
| Proximity and photoelectric switches | 24 V auxiliary | A few tens of mA each | Add up by quantity |
| Interposing relay coil | 24 V auxiliary | Holding current | Note the pick-up inrush |
| Solenoid valve coil | 24 V or external supply | Holding and inrush current | Use the simultaneous combination |
| Pushbuttons and lamps | 24 V auxiliary | A few to tens of mA each | Not negligible in quantity |
The aim of the accounting is that the supply never reaches the critical point of its rated output under any normal operating condition. At selection time the exact consumption of every module is often not yet available, so a first pass can be made from the manual nominal values with a generous margin and recalculated once the drawings are fixed. If, in service, a supply voltage dip alarm appears, or individual output points fail to operate when several switch at once, suspect the capacity accounting first, not the program.
The supply, protection and earthing requirements for the electrical equipment of machines follow GB 5226.1 and IEC 60204-1. The requirements for low-voltage switchgear and controlgear are given in the GB 14048 series, and the equipment requirements for programmable controllers refer to GB/T 15969.2 and IEC 61131-2. The 5 V and 24 V consumption of each module, the rated output of the supply and the derating curve are as stated in the manufacturer's manual.
Before adding or removing modules, connecting external loads or replacing the supply, switch off, prove dead and confirm no residual voltage; after the change, re-measure the supply voltage at each module and the base plate current. The final basis for supply margin should be the measured current.