How do you calculate the power supply capacity when selecting a PLC?

Working out the supply capacity means keeping two budgets apart. The DC 5 V inside the rack is fed by the power supply module; the field DC 24 V for sensors and output loads may come from the same module or from a separate switching power supply. The two budgets have different objects but share the rated output of one supply, so they must be added item by item with a margin on top. The sections below give the accounting basis, how to take the margin, and what to do when capacity is short.

1. First decide which current branches to account for

At least three branches have to be separated: the 5 V current on the backplane or base plate, which feeds the internal circuits of the CPU, I/O and communication modules; the 24 V auxiliary current, which feeds proximity switches, photoelectric sensors, interposing relay coils and pushbutton lamps; and the field load current carried independently by an external switching supply. What is being accounted for is whether the sum of the first two branches stays within the rated output of the power supply module; the third does not load the internal supply but must be checked for its own capacity and voltage drop.

2. How to calculate the 5 V current

I5V ≥ (ΣIeach module 5V + ΣIexpansion base and comms modules) × (1 + margin)

The 5 V consumption of each module is given separately in the manufacturer's manual and must be added module by module: the CPU, the power supply itself, each digital module, each analog module, the communication module and each expansion base all count. Estimating from the CPU nominal figure alone is not enough; once the rack is full the actual consumption often approaches or even exceeds the rated output of a small supply.

3. How to calculate the 24 V current

The 24 V side is mainly external devices. Each proximity or photoelectric switch is counted at the manufacturer's nominal current, usually a few tens of milliamperes each; each interposing relay and solenoid valve coil is counted at its holding current, with the inrush at pick-up noted separately; pushbutton lamps are counted at a few to a few tens of milliamperes each. These devices are numerous and their total is often larger than the 5 V side, which is why this branch is the one most easily forgotten. The 24 V rail is also often used as the load supply for digital outputs, and that part must be calculated for the worst simultaneous combination.

4. Margin and derating

The result must not be used right up to the rated value. As a working limit, about 60% to 70% of the rated output of the power supply module is usually taken, leaving the margin for temperature rise, supply fluctuation and later additions. When installed in a closed cabinet or at high ambient temperature, derate further, using the temperature curve given in the manufacturer's manual. Account also for the switch-on inrush and the worst case of simultaneous operation rather than an average load.

5. What to do when capacity is short

There are four options, in order of rising cost: move the 24 V field loads to an external switching supply to free internal capacity; refine the simultaneous-operation combination, using grouped delays to cut the instantaneous peak where necessary; fit a power supply module of larger capacity; or adopt distributed I/O or local field supply to spread the loads out. After any change, re-check the base plate current limit and the voltage drop.

6. Load current accounting reference

LoadSupply sourceCurrent basisKey point
CPU and the power module itselfInternal 5 VAs given in the manualAdd module by module, none omitted
Digital input moduleInternal 5 VAs given in the manualCount by module, not by point
Digital output moduleInternal 5 V plus 24 V loadInternal 5 V plus load currentKeep the two budgets apart
Analog moduleInternal 5 VManual value, larger for analogGrows with channel count
Communication moduleInternal 5 VAs given in the manualCount each card separately
Expansion baseInternal 5 VSum of the modules it carriesAdd to the main base total
Proximity and photoelectric switches24 V auxiliaryA few tens of mA eachAdd up by quantity
Interposing relay coil24 V auxiliaryHolding currentNote the pick-up inrush
Solenoid valve coil24 V or external supplyHolding and inrush currentUse the simultaneous combination
Pushbuttons and lamps24 V auxiliaryA few to tens of mA eachNot negligible in quantity

7. Notes

The aim of the accounting is that the supply never reaches the critical point of its rated output under any normal operating condition. At selection time the exact consumption of every module is often not yet available, so a first pass can be made from the manual nominal values with a generous margin and recalculated once the drawings are fixed. If, in service, a supply voltage dip alarm appears, or individual output points fail to operate when several switch at once, suspect the capacity accounting first, not the program.

8. References

The supply, protection and earthing requirements for the electrical equipment of machines follow GB 5226.1 and IEC 60204-1. The requirements for low-voltage switchgear and controlgear are given in the GB 14048 series, and the equipment requirements for programmable controllers refer to GB/T 15969.2 and IEC 61131-2. The 5 V and 24 V consumption of each module, the rated output of the supply and the derating curve are as stated in the manufacturer's manual.

9. Points to watch

⚠️ Three common traps:
(1) Estimating capacity only from the CPU nominal figure and omitting the 5 V consumption of each I/O and communication module, so the voltage sags once the rack is full;
(2) Hanging all the 24 V sensors and output loads on the internal supply, so the total exceeds the rated output and the machine appears unable to drive its loads;
(3) Accounting for an average load rather than the worst simultaneous combination, so the peak current exceeds the limit and causes occasional misoperation.

Before adding or removing modules, connecting external loads or replacing the supply, switch off, prove dead and confirm no residual voltage; after the change, re-measure the supply voltage at each module and the base plate current. The final basis for supply margin should be the measured current.