Normally-open (NO) and normally-closed (NC) have two identities: the physical identity of the field contact (closed or open when un-actuated) and the logical symbol in the ladder (using the signal itself or its inverse). Stack the two identities and beginners get lost — especially with the counter-intuitive "field NC button, program NO contact" pairing. The sections below untangle both layers and give selection rules.
| Identity | Meaning | Example |
|---|---|---|
| Physical NO | Open when un-actuated, closes when pressed | An ordinary start button |
| Physical NC | Closed when un-actuated, opens when pressed | E-stop and stop buttons |
| Program NO contact | Conducts when the input bit is ON | X0 ON conducts |
| Program NC contact | Conducts when the input bit is OFF (inverted) | X0 OFF conducts |
The crux is the signal's resting state: a physically NC button wired to an input keeps that input ON while idle; pressing it (E-stop tripping) turns the input OFF. The program reads the "disappearance" of the bit as the trip.
The wire-break safety principle: a safety signal must be "signal lost = fault detected". With a physical NC wired in, the input sits ON in normal operation, and a broken wire or an oxidised contact drops it OFF — the machine knows immediately. With a physical NO E-stop, the input is OFF in normal operation and pressing makes it ON; a broken wire leaves it OFF, the program thinks "not pressed", and the broken E-stop is undetectable. Therefore: E-stops, safety doors, overload and low-pressure signals are always physically NC.
An NC E-stop button wired to X0: idle, X0 = ON. To express "running allowed only while the E-stop is not tripped", draw a program NO contact with X0 in the start branch — X0 ON (no trip) conducts and allows running; a trip turns X0 OFF and breaks the branch. That is "field NC, program NO": the field inverts once, the program inverts once, and the logic returns to normal. Beginners who draw a program NC here find the machine "thinks the E-stop is tripped" the moment it powers up.
| Signal type | Field contact | Input resting state | Program treatment |
|---|---|---|---|
| Start button | NO | OFF | Take the press as an edge / NO logic directly |
| E-stop button | NC | ON | NO contact in the allow branch (conducts at rest) |
| Safety door switch | NC | ON | Like the E-stop: door open breaks it |
| Upper limit switch | By function | By design | Arrival = NO logic; over-travel protection = NC wiring |
| Run feedback | Contactor aux. NO | OFF → ON running | NO contact as the interlock |
NO/NC usage on internal relays M and outputs Y is pure logical inversion, unrelated to field wiring. Habits that keep logic readable: ① "when X then act" conditions in NO style; ② "forbidden unless X" conditions as NC contacts in series; ③ avoid stacking "NC contact + inverted coil" double negatives — readers will curse you.
| Question | If yes | Then |
|---|---|---|
| Can signal failure hurt people or the machine? | Yes (E-stop / door / over-travel) | Field NC + program designed as "signal lost = motion forbidden" |
| Is it an operator command? | Yes (start / reset) | Field NO, take the edge in the program |
| Is it a status feedback? | Yes (running / in position) | Design "active = doing"; NO wiring is fine |
| Does the signal hold long-term? | Yes (selector switch) | Use as a mode state; verify state at power-up |
Before running the program, enter monitor and exercise each field signal: press the start button and watch the X flick ON; release the E-stop and watch X go ON, press it and watch OFF — three minutes verifies every input's wiring, a hundred times faster than debugging a program flying on wrong inputs. Tick each point off against the drawing's signal table.
NO/NC is really "two kinds of inversion": the field contact inverts the physical action, the program contact inverts the signal bit. The NC field + NO program combination for E-stops aligns the dangerous direction with "signal lost" — every safety design rests on making failure visible rather than hidden.
NC wiring and wire-break detection for E-stop and protective signals follow GB 5226.1 / IEC 60204-1 and GB/T 16855.1 (ISO 13849-1); contact symbols and designations follow GB/T 4728 Graphical Symbols for Diagrams.
Add a column "field NO/NC + resting level" to the drawing's signal table, wire and program both against it; and always make per-point signal verification the first act of commissioning.