How do you design the safety functions and E-stop circuit on an OMRON NX1P2?

The conclusion first: the NX1P2 itself is not a safety controller. E-stop and related safety functions are carried by hard-wired safety relays or safety controllers, or — where conditions allow — by safety network slaves; the NX1P2 acts only as the "executing end" of the safety circuit (stopping axes, clearing outputs). The design principle in one sentence: the safety decision happens in the safety circuit, and the PLC is only informed of the result. The sections below cover the E-stop loop, stop categories, signal wiring and verification.

1. Basic architecture of the E-stop loop

Per GB 5226.1 (IEC 60204-1), E-stop is Category 0 (power removed immediately) or Category 1 (controlled deceleration first, then power removed). The typical arrangement: the E-stop button (normally closed contacts) is wired in series into a safety relay loop (e.g. OMRON G9SA), whose two output contact groups do two jobs — one directly cuts servo STO or the main contactor coil, the other feeds a "safety status" feedback signal into an NX1P2 input so the PLC can stop the process flow and clear output references.

The key point: the E-stop action chain does not pass through PLC logic — when the PLC is dead, the E-stop still removes power. That is the fundamental difference between a safety circuit and an ordinary control circuit.

2. Category 0 or Category 1 stopping

Stop categoryMethodSuitable cases
Category 0 (Cat.0)Immediate power removal (STO / contactor off)Small-to-medium inertia, stopping causes no secondary hazard
Category 1 (Cat.1)Controlled deceleration first (SS1-like), then power removalLarge inertia, vertical axes, high-speed rotating parts

Vertical axes must be protected against falling: pure STO with a brake that will not hold means the axis slides. Such axes either use the drive's SS1/SS2 safety functions with a brake sequence, or — when the safety relay triggers — the PLC first performs a decelerating stop, and the safety circuit removes power after the stop. Design this timing at the scheme stage; do not improvise during commissioning.

3. How safety signals enter the NX1P2

Only "results" enter the PLC, never "judgements": ① the safety relay's feedback contacts (K1-K2 loop monitoring) feed PLC inputs as interlock conditions for automatic start; ② safety door and light-curtain states likewise feed back through the safety circuit (or safety controller); ③ in the PLC program these signals are used for: no automatic start while the safety state is not restored, reset procedure (reset button + confirmation), and alarm logging. If a safety-network scheme is used (safety I/O slaves over a safety bus — support depends on the NX1P2 manual and Sysmac Studio version), the logic is configured on the safety side and the PLC still reads only the result.

4. Designing the reset loop

Reset is not restart: releasing the E-stop knob only removes the "fault condition"; a separate reset button (dedicated, recordable) triggers the reset procedure, and the reset signal must be edge-triggered only, never held. The reset loop is in series with every safety device's ready feedback — any one not restored makes the reset invalid. The standard flow: knob released → safety circuit self-check → PLC receives "safety ready" → operator presses reset → PLC performs a pre-start warning (horn + beacon for 3 s) → automatic start permitted.

5. Working with the servo drive's safety functions

FunctionRoleWiring / configuration
STOTorque off, motor coasts or holds on brakeSafety relay output to drive STO terminals
SS1Controlled deceleration then STODrive safety parameter setting + safety signal
SBC / brake controlLock the axis against fallingBrake sequence by drive or PLC cooperation — mandatory on vertical axes

The servo STO loop likewise uses dual-channel normally-closed wiring from the safety relay's two outputs; never take the "single-channel shortcut".

6. Commissioning and verification checklist

VerificationMethodPass criterion
E-stop pressedPress E-stop during automatic runPower removed immediately (or category-correct controlled stop), no secondary collision
PLC-dead simulationPLC power removed while E-stop pressedE-stop loop still removes power
Wire-break safetyOpen any single wire in the E-stop loopSafety relay declares a fault, start disabled
Reset procedurePress reset with knob not releasedReset invalid, no pre-start
Vertical-axis fallE-stop at heightSlip within allowance (brake effective)
Automatic restartStart automatic immediately after resetPre-start warning required, never silent auto-restart

7. Notes

The NX1P2's role in the safety system is "the informed party and process executor": the safety circuit judges danger and cuts power; the NX1P2 receives the signal and winds down the process (stop feeding, log alarms, manage reset). Writing the safety decision into PLC logic is the cardinal design sin — that is not a safety function, it is a control function.

8. References

E-stop and stop categories follow GB 5226.1 / IEC 60204-1; safety relays and STO loops follow GB/T 16855.1 (ISO 13849-1) and the OMRON G9SA / 1S-series drive safety manuals; NX1P2 input specifications and safety-network support follow its user manual.

9. Cautions

⚠️ Three traps to avoid:
① E-stop wired through normally-open contacts — a broken wire looks "normal" while the E-stop is dead; always normally-closed with wire-break detection;
② Putting the E-stop decision into the PLC scan — a dead PLC means a dead safety function;
③ Vertical axes with STO only and no brake sequence — the axis falls after E-stop and crushes the workpiece.

At drawing stage, keep the "safety circuit drawing" separate from the "control circuit drawing"; at acceptance, run the Section-6 checklist item by item and keep the record — a safety verification record is a mandatory delivery document.