The CJ1W-NC281 is a four-axis pulse-output position control unit for CJ-series racks: the PLC sends pulse + direction signals to stepper or servo drives to perform positioning. Three configuration tasks matter: axis parameters (electronic gear, homing), positioning sequences (target position and speed) and starting methods (sequence numbers or direct commands). The sections below follow hardware, parameters, sequences and commissioning.
The NC281 plugs into the CJ rack; confirm its first-word address in the CX-Programmer I/O table (it occupies several CIO words and a DM area). Each axis outputs PULSE and SIGN signal groups externally, with homing input (DEC/ORGI), dog signal (near point) and CW/CCW LIMIT inputs wired to the drive and sensors. The pulse output form (CW/CCW pulses or pulse + direction) is set in the axis parameters and must match the drive wiring.
Wire the limit switches hard into the unit's dedicated limit inputs — software limits cannot stop a machine that has lost position; hard limits are the last line of defence.
The core is two parameter groups, electronic gear and homing:
| Parameter | Meaning | How to set |
|---|---|---|
| Command pulses per revolution | Drive microstepping | Per the drive's switches or software |
| Travel per revolution | Lead screw pitch × gear ratio, or pinion circumference | Measured from the mechanical drawings |
| Electronic gear | Ratio between command pulses and travel | Aim for round numbers: 1 command unit = 0.001 mm or 1° |
| Homing method | Dog / origin stop / limit etc. | Match the installed sensors |
| Homing direction and speeds | High speed, creep speed | Low creep speed is what buys repeatability |
| Software limits | Positive / negative travel limits | Set about 5 mm inside the hard limits |
Parameters are sent via CX-Position or CX-Programmer and stored in the unit with power-off retention. After changing the electronic gear, every stored sequence's target values change meaning — a gear change forces a re-check of all sequences.
Sequences are organised by number: each defines target position, target speed, acceleration time, in-position window and dwell time. The program writes a "sequence number + start bit" via the unit's I/O, and the unit performs the trapezoidal move, returning Busy/Complete signals for the PLC interlocks. Three starting styles:
| Method | Suitable case | Program notes |
|---|---|---|
| Sequence start | Fixed station positions | Write sequence number → start → wait for Complete |
| Direct positioning | Target varies with product | Write the target to the designated DM words → direct start |
| JOG / inching | Setup and teaching | Move while held, stop on release, low speed |
Use "direct positioning" for product-variable lines and "sequence start" for fixed-takt lines; they can mix. A new start command during motion needs Complete first or a designed interruption logic — stacking blind starts alarms the unit.
① Manual JOG to verify direction and pulse equivalence: command 10 revolutions, measure mechanical travel, verify the scale factor; ② homing commissioning: confirm the dog/origin sensor active levels match the parameters, and repeatable homing within 1 command unit; ③ run one sequence at 30% speed, verifying acceleration and in-position signals; ④ ramp speed up to takt, watching for lost steps, stall and overshoot; ⑤ line integration with the interlock "no automatic start before homing complete".
| Symptom | Likely cause | Action |
|---|---|---|
| Motor does not move | Direction wiring reversed / enable missing | Check drive enable and SIGN wiring |
| Distance wrong | Electronic gear vs microstepping mismatch | Measure one revolution and back-calculate |
| Direction reversed | SIGN level logic vs parameter mismatch | Change output form or wiring |
| Home position drifts | Creep speed too high / sensor mount loose | Lower creep speed, secure the dog |
| Lost steps at speed | Pulse rate above drive limit | Lower max speed or raise microstepping |
| Overshoot at stop | Acceleration too short for load inertia | Lengthen accel/decel time |
| Software-limit alarm | Limits set wrong vs real travel | Reset to mechanical travel |
Pulse positioning is fundamentally "counting pulses": the controller issues a number of pulses, the drive moves a matching number of steps. So every accuracy problem reduces to two questions — is the pulse count right (scaling) and were any pulses lost (frequency/noise). Homing is the act of zeroing the count; with a stable zero, everything after it is stable too.
Configuration follows the OMRON CJ1W-NC281 Position Control Unit Operation Manual (axis parameters, positioning sequences); homing and limit protection follow GB 5226.1 / IEC 60204-1 requirements for moving mechanisms; pulse output ratings and address allocation follow the manual and catalogue.
Commissioning rhyme: verify equivalence, then home; run at 30% before full speed; never automatic without a home; hard limits always last.