The H5U takes analog signals through expansion modules: wiring and channel assignment are hardware work, while range calibration is the software work of "digital ↔ engineering" conversion. Keep the two separate and verify each segment, and analog problems become tractable. The sections below cover wiring, configuration, conversion and calibration; channel word addresses for each module model follow the corresponding chapter of the Inovance H5U User's Manual.
| Line | Connection | Notes |
|---|---|---|
| Module power | DC24 V supply terminals | Same 24 V rail as the PLC, capacity checked |
| Voltage input | VI+ and COM, e.g. 0~10 V | Low source impedance, not too long |
| Current input | II+ and COM, 4~20 mA | Current loops resist noise better — prefer them |
| Output channels | VO/IO and COM | Never mix voltage and current terminals |
| Shield | Earthed at one end to PE | Never earth both ends — circulating currents |
Use twisted shielded pairs, keep 20 cm or more from power lines (especially inverter outputs) or cross at right angles. 4~20 mA beats 0~10 V for noise, and the 4 mA live-zero distinguishes "real zero" from "broken wire" — prefer current signals.
Expansion modules are added in AutoShop's configuration view, or assigned channel addresses (IW/QW-type words) by the manual's default rules. Three points: ① modules plug to the CPU's right in fixed order — slot and address correspond one to one; ② set each channel's range type in the configuration to the actual signal; do not trust defaults; ③ the configuration downloads with the project; changing it requires a re-download.
The worst field habit is "wire first, read the manual later": discovering a wrong range type after wiring costs a rewire. List the signal types (voltage/current, span) in a table first, then wire, then configure.
The analog value arrives as an integer (full scale e.g. 0~4095 or 0~27648 — the exact range follows the module manual). Convert to temperature, pressure and so on:
4~20 mA signals add live-zero detection: a digital value below the 4 mA equivalent means "wire broken". The reverse conversion applies to outputs. Write the conversion once as a subroutine or function block and reuse it for every channel — per-point hand-rolled conversions drift apart in precision.
Sensors and modules both carry error, so perform a two-point calibration before commissioning: ① zero point: apply a known zero signal (e.g. 0.0 MPa from a standard pressure source) and record the deviation between the PLC reading and truth; ② full point: apply a near-full-scale known signal (e.g. 20 mA from a calibrator) likewise; ③ add offset and slope correction to the program conversion (linear two-point correction), or correct the transmitter directly. Archive the calibration record with date and instrument.
| Calibration item | Instrument | Acceptance (example) |
|---|---|---|
| Zero | Standard pressure source / calibrator | Deviation ≤ 0.5% of span |
| Full point | Calibrator at 20 mA | Deviation ≤ 0.5% of span |
| Midpoint spot check | 12 mA injection | Linearity deviation ≤ 1% of span |
| Break detection | Unplug the signal line | Alarm output, no false zero display |
Glitches come from field noise and the sensor itself; choose software filtering to suit: sliding average (mean of the last N samples, N = 4~16), first-order lag (new = old + α×(sample − old), α = 0.1~0.3), or rate limiting (discard spikes exceeding a threshold per scan). Stronger filtering means slower response — filter temperature hard, filter protective pressure lightly, according to the duty.
| Symptom | Likely cause | Action |
|---|---|---|
| Reading stuck at 0 | Wrong channel address / range configuration | Monitor the channel word online |
| Reading at full scale | Broken wire / over-range | Measure volts/amps at the terminals |
| Reading jitters | Noise / poor earthing | Check single-end shield earthing, reroute |
| Fixed offset | Zero drift | Redo two-point calibration |
| Wrong slope | Wrong full-scale constant in conversion | Verify the module's digital range in the manual |
| Output inactive | Channel word not written / clamped | Monitor output word and clamp logic |
| One channel dead | Oxidised terminal / failed module | Swap channels to verify, replace if needed |
The analog chain has four segments: physical quantity → sensor → module → program conversion. To locate faults, split at the terminals: measure the true signal there (is the sensor side right?), monitor the channel word (is the module side right?), check the conversion result (is the program side right?). Disciplined wiring plus two-point calibration settles ninety percent of "the reading is wrong" complaints.
Wiring and configuration follow the Inovance H5U Series PLC User's Manual and the relevant expansion module manual; channel word addresses and digital ranges follow the manual revision; cable routing and earthing follow GB 5226.1 / IEC 60204-1; calibration instruments require valid certificates.
Before handover, run the three-point check (zero, mid, full) plus the wire-break test; only when both pass does the machine go to the line. Tape the calibration record inside the panel door for the next maintainer.