What are the connection rules for expansion racks on Xinje XL series PLCs?

XL-series expansion (digital stacking, analog/temperature modules, CANLink remote expansion) follows rules that are simple but each one is a hard limit beyond which "weird faults" appear: total points, module count, address allocation, power budget and cable length. Checking these into the drawings at design time beats chasing strange symptoms during commissioning. The sections below cover local and remote expansion.

1. Local expansion: stacking rules

RuleContentConsequence if exceeded
Module countStacked directly right of the base unit, count capped per catalogueNot recognised or communication errors
Total I/O pointsBase + all expansions cappedModules beyond the cap do not work
Address allocationContinuous, automatic, by stacking orderInserting a module mid-train shifts every later address
Power budgetBase/expansion supply capability limitedVoltage droop at far points, false inputs
ConnectorsExpansion plugs seated, latches lockedIntermittent contact, whole I/O groups vanish

Automatic addressing is a double-edged sword: no manual addresses to set, but inserting a module in the middle shifts all following addresses and every reference in the program moves. Set the rule: modules are installed in drawing order, additions only at the end; a mid-train insertion forces a full review of address references.

2. Special rules for analog and special modules

When analog/temperature modules mix with digital ones: ① special modules occupy designated address blocks by position (see the catalogue mapping) — confirm actual addresses in the configuration or monitor before referencing them; ② analog modules draw significant 24 V current — sum the budget when several hang together; ③ some modules have placement requirements (e.g. after digital modules) — follow the manual's installation notes.

3. CANLink remote expansion: distributed I/O

For distant cabinets (multi-station machines, lines with two ends) use CANLink remote modules: the master at the PLC, slave modules out at the stations, bus-wired with twisted shielded pair. Rules: ① terminating resistors at both bus ends (many slaves have built-in DIP switches); ② cable length and station caps per catalogue; ③ every slave gets a unique station number — duplicates are the number-one cause of "the whole bus won't come up"; ④ keep the bus cable away from power lines, shield earthed at one end.

ItemLocal stackingCANLink remote
DistanceWithin the rack (centimetres)Up to hundreds of metres (per catalogue)
AddressingAutomatic, sequentialManual station numbers
Point capBound by base-unit limitsPer-slave points, bus capacity limit
Typical useExtra I/O in one cabinetDistributed acquisition and control across cabinets

4. The power budget: the step most often skipped

Expansion input commons and sensor supplies draw from the same 24 V, and each module adds backplane current. Sum three accounts: ① total 24 V current = all sensors + input optocouplers + module 24 V consumption; ② the base unit's backplane supply capability for expansions (per-point or per-module, from the catalogue); ③ the external 24 V supply sharing ground with the PLC. The classic symptom of overload is "with everything on, the last modules' inputs wander" — textbook voltage droop.

5. Installation and inspection checklist

CheckMethodPass criterion
Module orderCompare stacking order against the drawingIdentical
Connector seatingVisual + nudge the latchesNo skew, latches locked
Address verificationMonitor actual module addresses powered upMatch program references
Station numbersConfirm each remote module's DIPNo duplicates, match configuration
TerminatorsMeasure at both bus endsFitted at catalogue value
Supply measurementMeter the 24 V at the farthest point≥ 90% of nominal
Full-load testAll inputs active simultaneouslyNo input jitter or loss

6. Notes

Expansion connection is a triple budget: address space + power capability + physical link. Points and addresses decide whether it can connect, power decides whether it is stable, and connectors and cabling decide whether it stays reliable. Do the three sums on paper and the field becomes a plug-and-lights-on exercise.

7. References

Expansion capability, address mapping and power ratings follow the Xinje XL Series User's Manual and the CANLink Remote Expansion Module Manual; cable routing and shield earthing follow GB 5226.1 / IEC 60204-1 and bus installation practice; exact counts and length caps follow the model catalogue.

8. Cautions

⚠️ Three traps to avoid:
① Inserting a module mid-train during commissioning — all later addresses shift and the program misfires en masse;
② Two CANLink slaves on the same station number — the entire bus refuses to start;
③ Filling the rack without a 24 V power budget — inputs at the far end jitter under full load.

Write the handover rule on the drawing: expansions only appended at the end; a mid-train insertion forces a full program review. Print the CANLink station table for the panel door so nobody re-DIPs by guesswork.