The rated sensing distance on an inductive proximity switch datasheet is measured against a standard mild-steel target. With aluminium, brass or copper targets the usable distance drops to a fraction of that figure, so correction factors must be applied before fixing the mounting gap.
The switch drives a high-frequency field that induces eddy currents in the target. Because eddy-current loss differs by material, manufacturers state the nominal distance Sn for mild steel only. Apply 0.9~1.0 for cast iron, 0.7~0.85 for austenitic stainless steel, 0.4~0.5 for brass, 0.35~0.45 for aluminium and 0.25~0.35 for copper. An 8mm switch aimed at aluminium therefore reaches only about 3mm.
After multiplying by the material factor, derate by another 0.8 for temperature drift and manufacturing tolerance. Verify with an offcut of the real workpiece: approach the switch slowly, note the distance where the indicator lights, and repeat ten times. If the spread exceeds 0.2mm the factor or the switch is wrong. Set the working gap to 0.5~0.7 of the measured acting distance.
| Target material | Factor Km | Distance from 8mm rating | Recommended gap |
|---|---|---|---|
| Mild steel Q235 | 1.0 | 8mm | 4~5mm |
| Cast iron | 0.9~1.0 | 7.2~8mm | about 4mm |
| Austenitic stainless | 0.7~0.85 | 5.6~6.8mm | 3~4mm |
| Brass | 0.4~0.5 | 3.2~4mm | 1.5~2mm |
| Aluminium alloy | 0.35~0.45 | 2.8~3.6mm | about 1.5mm |
| Copper | 0.25~0.35 | 2~2.8mm | 1~1.5mm |
Use this table at selection time and again during installation: look up the factor, compute the effective distance, then fix the gap at half to two thirds of it. For high-volume aluminium or copper detection, pick a high-sensitivity type rated for non-ferrous targets instead of forcing a general-purpose unit.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Rated distance and test method per GB/T 14048.10 (IEC 60947-5-2); machine electrical safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.