Linear scale failures present as four patterns - position drift, count jumps, homing failures and signal alarms - rooted in contamination, interference or signal decay. A measurement-first path with numeric criteria avoids the guesswork.
Position drift: part dimensions creep while the semi-loop reads fine - clean the grating face first, since coolant crystals shift the interpolation phase; if cleaning fails, check loose mounting screws and a blocked thermal allowance. Count jumps: coordinates hop a few microns and return - measure amplitude with the scope; 1Vpp below 0.8V or TTL swing below 2.5V condemns cable or connectors, then check shield earthing and shared ducts. Homing failure on coded scales: verify homing speed and dog position, then whether the reference signal survives the input filter.
With a scope, half an hour settles it: 1Vpp phase amplitude 0.9~1.1V, Lissajous a clean circle - an ellipse sends you to the connectors; TTL differential swing 3~3.5V with rise time under 100ns, soft edges meaning overlength cable or stray capacitance. Without a scope, an AC multimeter reads roughly 0.35V RMS on 1Vpp. Alarm handling splits three ways: signal alarms (amplitude, wire break) - reseat connectors, test continuity, then replace the head, since eight in ten live in connectors; contamination alarms (following error) - clean face and wiper, then reset; configuration alarms - re-enter from the parameter sheet. Never silence the alarm by switching to semi-loop: the accuracy loss is invisible and every part ships subtly wrong, and running with a scraping head can destroy the grating.
| Symptom | First check | Action |
|---|---|---|
| Position drift | Grating fouling or loose screws | Clean the face and retighten |
| Count jumps | 1Vpp below 0.8V | Connectors and cable, rewire if needed |
| Homing failure | Reference filtered or dog shifted | Adjust homing speed and dog |
| Signal alarm | Connector contact, eight in ten | Reseat, continuity test, then new head |
| Following error | Fouling or gain mismatch | Clean, drop gain 20%, retune |
| Scraping noise | Gap lost or wiper damaged | Stop, reset gap, replace wiper |
The first rule of scale repair is measure before touching: waveform and amplitude data localise the fault faster than any swap. Keep a per-machine waveform archive so a new technician compares pictures instead of re-learning the machine, cutting diagnosis from half a day to half an hour.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Position detection and control circuits per GB/T 5226.1 (IEC 60204-1); signal transmission per the IEC 61158 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.