Capacitive sensors carry similar LEDs to inductive ones, but sensitivity drift moves the lamp state, so a bright lamp no longer proves correct detection. Learn the lamp codes, the sensitivity link and the two-wire reading rules.
Most capacitive units have one action LED, some add a power LED. The action LED follows the output: on NO types it lights with the medium detected and the output conducts, on NC types the opposite. The capacitive peculiarity is that the sensitivity potentiometer directly shapes the lamp: wound high, the vessel wall, fixtures or even a hand light the lamp as false targets; wound low, the real medium cannot. Always set mid-range and test with the actual medium before judging any lamp state - the key difference from inductive practice.
On two-wire capacitive units a faint idle lamp is normal, sustained by leakage current, while a fully lit idle lamp with false triggers calls for a leakage and sensitivity check before blaming the switch. A dark power LED points to reversed polarity or out-of-range supply - most capacitive types accept 10~30V DC wide range. Irregular flickering usually means powder on the face or a humidity step: clean first, then recalibrate. The lamp suits fast visual checks - approach and retract a test bottle, both directions - but it never replaces electrical verification, since a half-failed output transistor can light the lamp while starving the load; measure the output voltage monthly on critical stations.
| Lamp state | Likely meaning | Action |
|---|---|---|
| Action LED lit, NO type | Medium detected, output on | Normal, confirm load response |
| Action LED lit, NC type | Idle standby or inverted logic | Check the NO/NC definition |
| Steady lit at high sensitivity | Background treated as target | Set mid-range, retest with real medium |
| Faint idle lamp, two-wire | Leakage current, usually normal | Verify leakage under 1.5mA |
| Power LED dark | Reversed supply or out of range | Check 10~30V DC and polarity |
| Irregular flicker | Face contamination or humidity step | Clean face and recalibrate |
Judge the lamp together with the sensitivity setting: after every adjustment, sticker the housing with the dial position and turn count and check that position first at each inspection. A passing lamp check still deserves a monthly voltage measurement on critical stations; two layers of confirmation keep false trips and misses down.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Capacitive switch characteristics and tests per GB/T 14048.10 (IEC 60947-5-2); control circuits per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.