The operate and release points of a capacitive sensor never coincide - their gap is the hysteresis - and the scatter of repeated operate points is the repeatability. Both decide whether the unit is fit for level control and precise positioning.
Hysteresis H is the difference between the distance at which an approaching target triggers the output and the distance at which the receding target releases it. Standards allow 1 to 15 percent of the rated distance; real capacitive units sit at 3 to 10 percent. Hysteresis is deliberate anti-chatter design: without it an object hovering at the threshold makes the output oscillate violently. In through-wall level detection the hysteresis band doubles as a free control deadband of 3~10mm.
Repeatability is the spread of repeated operate distances under identical conditions, typically 1 to 2.5 percent of the distance, with good units reaching 0.25mm. It is governed by the medium and the environment: the dielectric constant is about 1 for air, 2~3 for paper, 2.3 for polyethylene and up to 80 for water, so changing the medium moves the operate point dramatically, and every 10 degrees of temperature adds another 0.5~1 percent of drift. Calibrate with the real medium, record the operate point A and release point R over ten cycles, and set the gap at 0.8 of A minus the expected drift.
| Parameter | Typical value | Field meaning |
|---|---|---|
| Hysteresis H | 3~10% of distance | Anti-chatter, usable as control deadband |
| Repeatability | 1~2.5% of distance | Precision jobs need 0.25mm units |
| Medium effect | Water 80 vs plastic 2.3 dielectric | Recalibrate on any medium change |
| Humidity effect | Millimetres of drift | Wet plants need shorter gaps |
| Temperature effect | 0.5~1% per 10 degrees | Calibrate hot machines hot |
| Calibration method | Range of 10 operate points | Swap the unit above 2.5% spread |
These limits make capacitive sensors right for on-off level duties and presence checks, not millimetre positioning. Recalibrate quarterly with the real medium, log operate point, release point and gap in the inspection sheet, and redo the calibration immediately after any change of medium recipe or plant environment.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Operating characteristics and tests for capacitive switches per GB/T 14048.10 (IEC 60947-5-2); control circuits per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.