Faults on two-wire DC switches like the E2E-X10D1-N cluster into four patterns: leakage-triggered phantom signals, residual-voltage undervoltage, reversed polarity and contaminated faces. A meter plus these thresholds resolves nine out of ten cases.
Pattern one, the downstream input lit with no target: measure standby leakage; above 1.5mA the switch or the cable insulation is leaking. Pattern two, no actuation with a target present: confirm a 12~24V supply and that the load current exceeds the minimum holding current of the switch. Pattern three, actuation with wrong lamp logic: check polarity first - reversed two-wire units survive but misbehave. Pattern four, drifting distance: clean the face and re-measure, since oil and iron dust can shrink a 10mm range to 6mm.
Localise by voltage segments. Across the switch: near supply voltage at idle, minus the 1~2V dropped by leakage through the load, and below 3V when conducting. Across the load: about supply minus 3V when conducting; a low drop means the relay cannot pull in firmly. Finally isolate the switch with a milliampmeter in series: idle current must stay below 1.5mA. After replacement respect polarity, keep at most two two-wire units in one series loop, and when driving PLC inputs confirm the input off-current exceeds the switch leakage - FX inputs typically release at 1.5mA, so move to three-wire types near the limit.
| Symptom | First check | Action |
|---|---|---|
| Lit with no target | Leakage above 1.5mA | Replace switch or fix cable insulation |
| No actuation | Supply under 12V or load current too small | Check supply and minimum load current |
| Inverted lamp logic | Reversed polarity | Rewire brown positive, blue negative |
| Distance drift | Measured range down over 30% | Clean face; replace if still drifting |
| Relay chatters | Residual voltage above 3V | Shorten series loop or use low-residual type |
| Half-lit PLC input | Leakage near off-threshold | Move to three-wire or add bleeder resistor |
The whole method rests on two numbers - leakage and residual voltage - so carry a meter that reads milliamps and most faults fall within ten minutes. Log measured values, not just conclusions; three months of records exposes aging switches early enough for planned replacement instead of a breakdown stop.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Two-wire switch characteristics and tests per GB/T 14048.10 (IEC 60947-5-2); control circuits per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.