The switch sees no target yet the output stays on and the PLC keeps reporting material - the causes cluster and are findable. Six origins, a quick discrimination method and the matching fixes, in probability order.
Six causes ranked by likelihood: iron dust and oily sludge filmed on the sensing face acting as a permanent target, commonest in wet machining; a punched-through output transistor after a load short or overvoltage surge; two-wire leakage above the load threshold from damp cable or a leaky switch; residual background, where fixed metal near the mount was never verified as clear; a type mix-up, running an NC unit where NO logic is expected - idle conduction is by design; and a PLC input common wired wrongly, making the loop conduct with no fault in the switch at all.
Discriminate from simple to deep in three steps. Detach the load and meter the switch directly - series a milliampmeter between output and supply with no target: conducting means the switch body is guilty, not conducting points downstream. Clean the face and retest: still conducting after cleaning means a punched transistor or leakage - replace. Then check background and type: confirm no fixed metal within three times the sensing distance, verify the NO/NC suffix, and measure two-wire leakage against the 1.5mA mark. Fixes follow: clean plus a dust shroud or coated type in oil mist; replace the switch and hunt the load short or surge, fitting a freewheeling diode across inductive loads; re-cable or move to three-wire on leakage; relocate or flush-mount against background; fix the program or swap the type on the mix-up. Prevention: monthly face cleaning in wet zones, a no-target output check written into every installation acceptance, and fuse or current limiting on the load side so the next short does not kill the new switch.
| Cause | Discrimination | Fix |
|---|---|---|
| Iron dust on the face | Recovers after cleaning | Clean, add shroud; coated type in mist |
| Transistor punched | Still on with load detached | Replace; hunt shorts and surges |
| Leakage above threshold | Idle current over 1.5mA | Re-cable or move to three-wire |
| Residual background | Recovers when metal removed | Relocate or flush-mount |
| NC used as NO | Check the type suffix | Adjust logic or swap the unit |
| Wrong input common | Input state with switch removed | Rewire per sinking or sourcing rules |
The discipline is to detach the load first and split the responsibility - switch, background or wiring - in one move instead of blind swaps. Prevention centres on cleaning and background verification: write the no-target check into the acceptance sheet for every new installation.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Output characteristics and tests per GB/T 14048.10 (IEC 60947-5-2); control circuits per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.