How to tell normally open from normally closed on capacitive proximity sensors

Capacitive proximity sensors ship in NO and NC versions that look identical from outside. Misreading the contact logic turns a simple swap into a crashed axis, so verify the output behaviour before wiring it into the PLC.

1. How it works

Start with the type suffix: most makers mark NO (normally open) or NC (normally closed) on the label, sometimes with a contact symbol. When the marking is worn off, test electrically. For a three-wire sensor, power it up and measure the black output wire against 0V with a DC voltmeter: an idle NO unit sits near 0V while an idle NC unit sits near supply voltage.

2. Practice and pitfalls

Bring a grounded metal block or a water-filled plastic bottle near the face. A NO output jumps above 20V on a 24V supply; an NC output drops to the residual voltage of about 3V or less. For two-wire types, read the voltage across the sensor in series with the load: a large idle drop means leakage through a closed contact, and the drop falls to the residual level when the unit actuates.

3. NO versus NC quick test table

Test meansNO behaviourNC behaviour
Type labelMarked NOMarked NC
Idle output, 3-wireNear 0VNear 24V supply
Triggered output, 3-wireAbove 20VResidual below 3V
Action indicatorLights on detectionGoes dark on detection, verify by test
Two-wire idle dropNear supply voltageNear supply, drops on actuation
PLC input logicInput sets to 1 when triggeredInput sets to 0 when triggered

4. Notes

Set the sensitivity potentiometer to mid-range before testing, use a grounded metal piece or a water container as the target, and write the conclusion on the housing and into the machine file, so replacement orders cite the same suffix and the PLC logic stays consistent.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contact marking and testing per GB/T 14048.10 (IEC 60947-5-2); control circuits per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Concluding before adjusting sensitivity:Background triggers invert the NO or NC reading - set mid-range first
② Using a dry fingertip as target:Body capacitance is marginal - use a grounded metal block or a water bottle
③ Swapping in an NC unit without logic check:The input logic flips and the machine can crash on first move

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.