Capacitive proximity sensors ship in NO and NC versions that look identical from outside. Misreading the contact logic turns a simple swap into a crashed axis, so verify the output behaviour before wiring it into the PLC.
Start with the type suffix: most makers mark NO (normally open) or NC (normally closed) on the label, sometimes with a contact symbol. When the marking is worn off, test electrically. For a three-wire sensor, power it up and measure the black output wire against 0V with a DC voltmeter: an idle NO unit sits near 0V while an idle NC unit sits near supply voltage.
Bring a grounded metal block or a water-filled plastic bottle near the face. A NO output jumps above 20V on a 24V supply; an NC output drops to the residual voltage of about 3V or less. For two-wire types, read the voltage across the sensor in series with the load: a large idle drop means leakage through a closed contact, and the drop falls to the residual level when the unit actuates.
| Test means | NO behaviour | NC behaviour |
|---|---|---|
| Type label | Marked NO | Marked NC |
| Idle output, 3-wire | Near 0V | Near 24V supply |
| Triggered output, 3-wire | Above 20V | Residual below 3V |
| Action indicator | Lights on detection | Goes dark on detection, verify by test |
| Two-wire idle drop | Near supply voltage | Near supply, drops on actuation |
| PLC input logic | Input sets to 1 when triggered | Input sets to 0 when triggered |
Set the sensitivity potentiometer to mid-range before testing, use a grounded metal piece or a water container as the target, and write the conclusion on the housing and into the machine file, so replacement orders cite the same suffix and the PLC logic stays consistent.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contact marking and testing per GB/T 14048.10 (IEC 60947-5-2); control circuits per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.