The temptation to save a signal splitter by stringing one more instrument on the loop breaks the voltage budget quietly, and the high end of the scale starts lying before anyone notices.
A 4-20 mA loop shares one current, so series devices are legal in principle, but voltage decides: total load resistance times 20 mA must stay below supply voltage minus the transmitter minimum working voltage. The formula is Rmax = (Vsupply − Vmin) divided by 0.02; with 24 V supply and a 10 V transmitter that allows 700 ohms. Typical burdens: an AI input at 250 ohms, an isolator at 50 to 100, a recorder at 100 to 250, plus 10 to 50 of cable and terminals. Three extras already approach the ceiling, and a fourth starves the transmitter at 20 mA, distorting the top of the range.
The symptom is deceptive: readings are fine from 4 to 12 mA while the 16 to 20 mA segment sags or goes nonlinear, with errors of 2 to 5 percent near full scale. Consequences: understated high end metering, unstable control from an undervolted transmitter, and intermittent faults that follow supply fluctuations and resist troubleshooting. The classic case is a loop carrying isolator, barrier and recorder, then absorbing one more passive instrument during a retrofit, while winter raises copper resistance for good measure. Every loop modification gets a fresh load budget, because lighting up is not the same as working.
The rule: transmitter plus AI input is the base, at most one series device, with the total kept at 80 percent of the computed maximum. For multiple consumers, do it properly: a splitter or isolating distributor feeding independent loops, a dual output transmitter where supported, or software distribution inside the DCS from one input. Intrinsically safe loops add the barrier drop and follow the certificate figures, with an even tighter budget. At acceptance, run a full scale test: a stable 20 mA with a correct high end reading is the only proof the budget holds.
| Device | Typical load | Notes |
|---|---|---|
| AI channel input | 250 ohms | Standard sampling resistor |
| Isolator input | 50~100 ohms | Per datasheet |
| Recorder input | 100~250 ohms | Per model |
| Safety barrier | Per certificate | Drop included, mandatory for IS loops |
| Cable and terminals | 10~50 ohms | Grows in winter on long runs |
| Allowed total | (Vsupply−Vmin)/0.02 × 0.8 | 24 V, 10 V transmitter ≈ 560 ohms |
Use this table when budgeting loop loads for modifications and series connections. Compute before any series addition, keep 20 percent margin, cap at one intermediate device, and split multiple consumers through distributors. Full scale testing at acceptance is the proof, and IS loops add barrier figures to the arithmetic.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Loop design per GB/T 17614.1; electrical safety per GB/T 5226.1 and IEC 60204-1; IS loops per GB/T 3836 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.