Both are high accuracy liquid meters, but one insists on conductive liquid and the other on clean liquid. Choosing the wrong principle wastes the whole budget, so the boundary is drawn by conductivity, viscosity and solids content.
An electromagnetic meter works by Faraday induction and demands conductivity above 5 microsiemens per centimetre: tap water at 200 to 500 is fine, while pure water, oils and hydrocarbons are invisible to it. Its strengths are no moving parts, no obstruction, near zero pressure loss, corrosion resistant liners and long life. A turbine meter is mechanical and indifferent to conductivity, so oils, solvents and alcohols are its home ground, with accuracy to plus or minus 0.2 to 0.5 percent. But bearings hate grit, viscosity above about 5 mm²/s shifts the K factor noticeably, and heavy oils need calibration on the actual liquid. Abrasive slurries chew rotors and belong to electromagnetic meters.
On numbers: electromagnetic accuracy is plus or minus 0.5 percent class with turndown of 1:20 to 1:40, still reliable down to 0.3 m/s. Turbine accuracy reaches plus or minus 0.2 to 0.5 percent after liquid calibration, turndown is typically 1:10, and bearing friction shows first at low flow. Pressure loss is zero for electromagnetic and grows with flow squared for turbine, which matters on low pressure systems. Maintenance is minimal for electromagnetic, while turbine lives on strainer cleaning, bearing checks and 1 to 2 year reverification, paced by its moving parts.
Screen the service on three questions: conductivity, which excludes electromagnetic below 5 microsiemens per centimetre; viscosity and cleanliness, which exclude turbine; then temperature and pressure, which limit turbine internals and electromagnetic liners and electrodes. Typical split: sewage, cooling water, acids, alkalis and slurries go electromagnetic; oils, solvents and alcohols go turbine or positive displacement. Conductive slurries suit electromagnetic but watch liner wear, keeping velocity above 2 m/s to avoid wearing through. When neither fits, move to Coriolis or positive displacement rather than compensating a wrong principle.
| Item | Electromagnetic | Turbine |
|---|---|---|
| Medium requirement | Conductivity above 5 uS/cm | Any conductivity, clean and thin |
| Accuracy | ±0.5% class | ±0.2~0.5% with liquid calibration |
| Turndown | 1:20~1:40 | Typically 1:10 |
| Pressure loss | Nearly zero | Present, grows with flow squared |
| Moving parts | None | Rotor and bearings |
| Typical media | Sewage, acids, slurries | Oils, solvents, alcohols |
Use this table for principle selection on liquid duties. Measure or look up conductivity first, then viscosity and solids, then check temperature and pressure against liner and electrode materials. If neither principle fits, go Coriolis or positive displacement instead of compensating a bad choice.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electromagnetic verification per JJG 1033; turbine per JJG 198; electrical safety per GB/T 5226.1 and IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.