Unexplained reading jitter usually turns out to be common mode voltage: both signal conductors moving together against earth. Telling common mode from differential, measuring it, and then breaking the path are the whole game.
Differential voltage is the wanted signal between the two conductors; common mode is their shared voltage to earth. Sources include earth potential differences between field and control room, reaching several volts, converter leakage and stray currents from large drives. AI channels tolerate roughly plus or minus 12 to 15 V of common mode before saturating and distorting. The advertised CMRR of 80 to 100 dB assumes balanced arms, so unbalanced lead resistances or broken shields discount it heavily, and whatever imbalance exists converts common mode into differential, which is exactly the jitter mechanism.
Diagnose in three steps. Measure each conductor to earth with a DC meter: values that move together with plant load signal common mode, while healthy loops sit near zero. Compare the voltage between conductors with the DCS reading: a stable field voltage with a jumping DCS points at the channel or earthing. Scope the waveform: 50 Hz envelopes and harmonics mean mains coupling, tens of kilohertz spikes mean converter switching noise. Locate the source by disconnecting the field side and watching stability, and by temporary shield earthing experiments, always restored afterwards, working segment by segment.
Suppress by effect. Isolation first: a three port isolator rated 1.5 kV or better cuts the ground loop entirely, costing money but ending the problem. Equipotential bonding second: a heavy copper bar tying field earth to control room earth drives the potential difference under 1 V. Third, confirm the AI channel is truly differential, since single ended inputs fear common mode by design. Fourth, wiring remediation, moving signal runs 300 mm from power cable and restoring single end shield earthing. Around converters, add isolators preventively, because software filtering only slows the jitter and never removes the cause.
| Step | Method | Criterion |
|---|---|---|
| Measure common mode | Each conductor to earth | Near zero normally, moving means trouble |
| Compare readings | Field voltage versus DCS | Stable field with jumping DCS means channel |
| Scope the waveform | Look for 50 Hz and spikes | Mains envelope means earth coupling |
| Locate the source | Disconnect segment by segment | Field side versus channel side |
| Isolate | Three port isolator, 1.5 kV | Ground loop fully cut |
| Bond the earths | Copper bar between earths | Potential difference under 1 V |
Use this table when chasing analogue signal jitter. Qualify with a common mode measurement, locate segment by segment, then treat with isolation, bonding and wiring in that order. Preventive isolation around drives is cheapest in the end, and software filters never fix a live ground loop.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: EMC for measurement equipment per GB/T 18268 (IEC 61326); electrical safety per GB/T 5226.1 and IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.