The pulse equivalent links counts to physical travel on magnetic encoders and scales, and one wrong decade in the setting lies about every position. Construction of the equivalent, conversion formulas and a worked example below.
Magnetic scales arrange their signal in magnetic pole pitches, typically 2mm; the head reads the field with sine-cosine outputs and an interpolation circuit turns them into pulses. The equivalent is pitch divided by cycles-per-pole times electronic interpolation: 2mm pitch, one cycle per pole, 4000-fold interpolation gives 0.5µm per pulse. Rotating magnetic encoders work the same way with poles per revolution. Every link in the chain - pitch, cycles, interpolation - shifts the equivalent, so the value programmed into the CNC must match the hardware chain exactly; that correspondence is the mathematical basis of closed-loop position.
Conversion: travel equals count times equivalent. Worked example: 0.5µm per pulse and a counter at 1,000,000 gives 500mm; reversing, an 800mm stroke needs 800 divided by 0.0005, or 1.6 million counts - size the counter and data format from the maximum stroke, and 32 bits is ample. Speed example: a 10mm screw at 500mm/s with a 2000-count-per-rev encoder on the screw end produces 100,000 pulses per second - check the controller counting rate covers it. Setting verification: after configuring, move a known distance measured with a dial gauge or gauge block and compare; error within 0.1 percent passes, a factor of ten means a wrong decade, a factor of two points at the interpolation setting. The classic errors: DIP switches moved without updating parameters, a 1mm-pitch tape configured as 2mm showing half distance, and inch-millimetre confusion in the equivalent. Prevention: a nameplate beside the scale stating pitch, interpolation and equivalent, plus a photo of the switch block after every change.
| Parameter | Example value | Conversion note |
|---|---|---|
| Magnetic pitch | 2mm | Per the tape nameplate |
| Interpolation | 4000 | Set in the box or head |
| Pulse equivalent | 0.5µm per pulse | Pitch over interpolation |
| Stroke capacity | 800mm needs 1.6M counts | Size from maximum stroke |
| Speed check | 500mm/s needs 100k pulses per second | Against controller counting rate |
| Verification | Real move versus dial gauge, within 0.1% | Mandatory after any setting |
Equivalent setting means making counts and millimetres agree one to one: compute on paper, post it on a nameplate, verify by real measurement - after those three steps, equivalent faults vanish. Keep a parameter card with the full chain inside each cabinet, so a dead control can be refilled from the card without re-deriving.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Digital readout systems and control circuits per GB/T 5226.1 (IEC 60204-1); accuracy acceptance per the relevant national standards. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.