Absolute encoders cannot miscount by design, so field position drift almost always lives on four lines: battery, interference, communication or mechanical slip. Here is the probability-ordered hunt with numeric criteria.
Suspect one on battery-backed multi-turn units: the 3.6V lithium cell alarms below 3.1V on most drives, but a mis-set or masked threshold lets it slip through. Read the cell voltage in the drive diagnostics and plan replacement below 3.3V; verify the alarm threshold is set and not inhibited. A depleted cell loses the turns while the single-turn angle survives - the signature is a position offset by whole revolutions after power-down, with in-turn motion still correct. Replace the cell live and run a reference check afterwards.
Suspect two is interference and communication: absolute units speak serial protocols (EnDat, BiSS, SSI), and poor shielding or messy earthing produces bit errors seen as position jumps or comms alarms. Three steps: earth the shield at one point only, verify it on both ends of the run; keep the encoder cable 200mm from power runs with 90-degree crossings; and replace any improvised unshielded extension - temporary test leads left in place are the classic trap. SSI jitter shows as low-bit flutter, EnDat reports CRC errors - read the error counter before touching hardware. Suspect three is mechanical slip: a loose coupling or hollow-shaft clamp means the encoder is honest about a shaft that slipped. The signature: drift direction correlates with load torque, and overnight offsets correlate with temperature change. Check coupling screw torque, replace worn jaw inserts, torque hollow-shaft clamping rings at 5~8N·m per the manual, and verify the coupling rating for hard-stopping inertial loads. Only after all three lines are clear is the encoder itself guilty.
| Suspect line | Criterion and value | Action |
|---|---|---|
| Battery voltage | Plan below 3.3V, alarm at 3.1V | Replace live, verify reference |
| Comms bit errors | Growing CRC counter | Single-point shield earth, restore original cable |
| Shield earthing chaos | Earthed at both or many points | Re-earth at the drive end only |
| Coupling slip | Drift follows torque direction | Torque or replace the coupling |
| Hollow-shaft clamp | 5~8N·m per manual | Retorque with thread marks |
| Encoder itself | Drift persists after three lines | Repair or replace, redo reference |
The chase order is battery, communication, mechanics, then the encoder - the first three cover nine in ten cases and are field-fixable. Run a battery ledger and a monthly comms-error record; data first, hands second, and absolute-system reliability becomes a managed outcome rather than luck.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Serial encoder interfaces per the IEC 61158 series; control safety and earthing per GB/T 5226.1 (IEC 60204-1). Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.