Pick the wrong material and the vapour alone pits the diaphragm within months; pick the wrong principle and foam or vapour blinds the sensor completely. Level measurement on chemical tanks is decided by corrosion class first and measurement principle second, in that order.
Sort the service into four corrosion grades before opening any catalogue. Grade one, water based liquids and oils, suits magnetic level gauges with 316L or radar. Grade two, volatile organic solvents such as benzene, alcohols and ketones, calls for radar or servo gauges and rules out ultrasound because vapour absorbs sound. Grade three, inorganic acids like HCl and H2SO4, needs radar with PTFE antenna covers and PTFE lined magnetic gauges. Grade four, wet chlorine and hypochlorite, leaves non-contact radar with full PTFE treatment as virtually the only robust route. Check every wetted part against the worst case, including cleaning and drainage with concentrated media, not the steady state.
Non-contact radar is the default for corrosive tanks: the antenna never touches the liquid, a PTFE parabolic dish on a 316L flange shrugs off nearly all acid mist, and accuracy is plus or minus 1 to 3 mm within 30 m. Low dielectric media below 1.5, such as LNG and light hydrocarbons, reflect too weakly and need a stilling well. For contact types, a PTFE lined magnetic gauge suits local indication, though float sticking is the usual complaint; hydrostatic probes with silicone capsules survive months, not years, in strong acid. Ultrasonic devices are effectively eliminated by vapour and foam.
High level interlocks must be independent of the continuous transmitter: fit a separate switch with its own signal path, because a drifting transmitter plus a shared signal is how tank overfills happen. Keep the nozzle clear of fill points, agitators and heating coils, and clean stilling wells regularly since 2 mm of wall coating generates false echoes. Use Ex rated instruments at the tank roof and purge the antenna cover where condensation forms.
| Media type | Recommended scheme | Avoid |
|---|---|---|
| Water based or oils | Magnetic gauge 316L or radar | Ultrasound, foam interference |
| Volatile solvents | Radar or servo gauge | Ultrasound and hydrostatic probes |
| HCl and H2SO4 service | Radar with PTFE antenna, PTFE lined gauge | Bare 316L wetted parts |
| Wet chlorine, hypochlorite | Non-contact radar, full PTFE | Any metal diaphragm contact type |
| Low dielectric light ends | Radar with stilling well | Plain radar, weak echo |
| High viscosity, coating media | Guided-wave radar cable type | Ultrasound and displacers, sticking |
Use this table during tank farm revamps and new tank instrument reviews. Fix the principle by corrosion grade, the Ex rating by zone classification, and add an independent high level switch for the interlock. List every wetted material in the design file and verify material certificates item by item at procurement.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Fire protection and interlock layout per GB 50160; Ex equipment per GB/T 3836.1; machine electrical safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.