A 0-20 mA loop differs from 4-20 mA only by the missing live zero, yet every shielding and earthing rule still applies, and a broken wire now looks exactly like a true zero. The craft lies in the shield discipline and the zero management.
Shielding matches the 4-20 mA rulebook: twisted shielded cable earthed at a single end, the control room side on the signal earth bar, field end trimmed and floating. Earthing both ends builds a ground loop that feeds mains interference straight into the loop, and a field side shield brushing the enclosure quietly recreates the same fault, so retrofit work verifies shield to earth insulation loop by loop. Coverage must be complete, with shield continuity carried through junctions on shield terminals rather than broken open, and loops beside converters or power runs gain a metal conduit on top of 300 mm separation.
The earthing system separates two families: signal earth as the analogue reference and protective earth for enclosure safety, kept apart and joined at a single point. Mount the signal earth bar insulated from the cabinet to prevent multipoint earthing; intrinsically safe loops keep their own bar per the certificate. Earth potential difference is the invisible interference source, so cross plant loops use isolators that cut the ground loop with each end referencing its own earth, the standard arrangement for long 0-20 mA runs.
The zero is the structural weakness: 0 mA is both a genuine zero and a broken wire, indistinguishable, so the DCS shows a confident zero that is really a dead loop. Manage it by moving important loops to 4-20 mA with its 3.6 mA break detection, or by loop monitoring that samples a series resistor to prove continuity, or at minimum by alarm logic set above the smallest plausible process value. Calibration carries its own trap: full scale is 20 mA, so divide by 20, not the 16 of a 4-20 mA span, because the wrong coefficient skews every reading by 25 percent.
| Item | Rule | Key point |
|---|---|---|
| Shield earthing | Single end at control room | Trim field end clean |
| Shield continuity | Shield terminals through junctions | Never broken mid run |
| Signal earth system | Separate from PE, single point join | Insulated bar |
| Cross plant loops | Isolator cuts the ground loop | Independent earths |
| Break detection | Live zero or loop monitoring | Separate zero from bad value |
| Span conversion | Full scale is 20 mA | Distinct from the 16 of 4-20 mA |
Use this table for 0-20 mA construction and operation. The shielding and earthing rules mirror 4-20 mA exactly, the zero ambiguity gets covered by live zero, loop monitoring or alarm floors, and span arithmetic divides by 20. Move important loops to 4-20 mA where possible and write break management into the operating procedure for the rest.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical safety and earthing per GB/T 5226.1 and IEC 60204-1; EMC per GB/T 18268 (IEC 61326). Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.