Both are non contact level instruments separated by a factor of two or three in price, but the accuracy and stability gaps are real and they come from physics, not marketing. The question is when ultrasound is good enough and when radar is mandatory.
Ultrasound measures distance by acoustic time of flight, so the speed of sound matters: about 343 m/s in air at 20 degrees C, changing roughly 0.17 percent per degree C. Built in temperature sensing compensates most of it, but vapour composition still bends the sound speed. Typical accuracy is plus or minus 10 to 30 mm or 0.2 to 0.5 percent of span. Radar uses electromagnetic waves at 26 or 80 GHz whose speed is indifferent to the medium: high end units reach plus or minus 1 to 3 mm, guided wave versions approach half a millimetre. Radar owns the accuracy ceiling, especially on tanks with wide temperature swings or unstable vapour.
The failure lists separate the two. Ultrasound dies in vacuum, where sound cannot travel; at high pressure, where sound speed shifts; in foam, which absorbs it; in dense vapour, which attenuates it. Radar fails far more rarely: very low dielectric media below about 2 for 26 GHz units, condensation coating the antenna, and foam still bothers guided wave versions. Thermal drift is essentially absent in radar. Vacuum vessels, pressurised reactors and agitated, foaming tanks must use radar; clean ambient water and effluent duties run perfectly well on ultrasound at a third of the price.
Decide with a checklist first: vacuum, high pressure, foam, heavy vapour, dust, wide temperature swings, any hit means radar. Compare prices only when the checklist is clean, with ultrasound at one half to one third of radar cost. Maintenance differs too: ultrasonic faces need periodic scale cleaning, radar antennas foul depending on the medium. Do not save money by putting ultrasound on a heavy vapour tank, the signal fades year by year until the tank goes blind, and retrofitting costs far more than the difference. Equally, radar on a clean water pond is precision nobody uses.
| Item | Ultrasonic | Radar |
|---|---|---|
| Principle | Acoustic time of flight with compensation | Electromagnetic time of flight |
| Typical accuracy | ±10~30 mm or ±0.2~0.5% FS | ±1~3 mm, guided wave ±0.5 mm |
| Temperature effect | Visible, needs compensation | Essentially none |
| Foam and heavy vapour | Fails outright | Radar works, mind guided wave in foam |
| Vacuum and pressure | Not usable | Usable |
| Price | 1/2~1/3 of radar | Higher, 26 GHz in the thousands |
Use this table to allocate level instrument budgets sensibly. Run the duty checklist first and go radar on any hit; keep ultrasound for clean ambient water and effluent when the list is clear. At acceptance, verify against actual liquid under real conditions, and for ultrasound watch the readings through temperature swings.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: General requirements per GB/T 5226.1 and IEC 60204-1; Ex areas per GB/T 3836.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.