Analogue signal wiring practice and terminal definitions

Reversed polarity, chaotic shield earthing and unclear terminal assignments cause most analogue loop trouble during commissioning. The rules are few and strict, and they apply from the first wire pulled.

1. How it works

Two wire 4-20 mA transmitters share power and signal over two conductors, powered by the DCS or PLC channel, so wire plus to plus and minus to minus per the channel document; reversed, the transmitter stays dead, and a few models suffer damage. Four wire transmitters split supply and signal, and the channel must have its excitation disabled, otherwise channel 24 V fights the external supply and blows the fuse. The classic mistakes are wiring a two wire instrument into an excited channel, or feeding a four wire signal into one, both ending in blown fuses, so identify the channel type before any wire lands.

2. Numbers and practice

Shielding follows one rule: twisted shielded cable earthed at a single end, the control room side on the signal earth bar, with the field end trimmed, insulated and floating, because earthing both ends builds a ground loop that imports mains interference. Separate analogue signal cable from power runs by at least 300 mm in parallel and cross at right angles where crossing is unavoidable. Keep signal earth separate from protective earth, joined at one point; frequency converter earths follow their own rules and never borrow the signal bar. Intrinsically safe loops keep a dedicated earth bar and resistance per the certificate, never mixed with ordinary signal earths.

3. Pitfalls and fixes

Terminal verification is mandatory before startup: check every point between drawing and reality with a continuity meter, tick and sign the record, and confirm transmitter polarity, channel polarity and shield terminals all agree. At energisation, measure loop current in series, expect 4 mA at zero, then compare the DCS reading with a handheld communicator and verify range configuration. The recurring traps: legacy modifications where drawings and reality diverge, causing crossed signals that eat hours, and a field side shield brushing the enclosure, which reimports the ground loop despite doing everything else right.

4. Analogue wiring quick table

ItemRuleConsequence if broken
Two wire wiringChannel powered, plus to plusDead loop or damaged transmitter
Four wire signalDisable channel excitation firstDual supply conflict, blown fuse
Shield earthingSingle end at control roomGround loop interference
Distance from powerSeparate trays, 300 mm parallelMains coupling, jumping readings
Terminal checkPoint by point continuity versus drawingCrossed signals eat hours
IS loopsDedicated bar per certificateMixed earths break intrinsic safety

5. Notes

Use this table for self checking and acceptance of analogue loop wiring. Identify the channel type first, earth the shield at one end, verify terminals point by point with records, and prove the loop by current plus DCS display. Retrofit projects deserve double care, since history hides between the drawing and the cabinet.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Wiring and safety per GB/T 5226.1 and IEC 60204-1; intrinsically safe loops per GB/T 3836 series. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① A two wire instrument on an excited channel blows the fuse before the loop ever works
② Earthing the shield at both ends imports mains noise that keeps readings jumping
③ Unchecked legacy terminals cross signals and eat commissioning hours

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.