Reversed polarity, chaotic shield earthing and unclear terminal assignments cause most analogue loop trouble during commissioning. The rules are few and strict, and they apply from the first wire pulled.
Two wire 4-20 mA transmitters share power and signal over two conductors, powered by the DCS or PLC channel, so wire plus to plus and minus to minus per the channel document; reversed, the transmitter stays dead, and a few models suffer damage. Four wire transmitters split supply and signal, and the channel must have its excitation disabled, otherwise channel 24 V fights the external supply and blows the fuse. The classic mistakes are wiring a two wire instrument into an excited channel, or feeding a four wire signal into one, both ending in blown fuses, so identify the channel type before any wire lands.
Shielding follows one rule: twisted shielded cable earthed at a single end, the control room side on the signal earth bar, with the field end trimmed, insulated and floating, because earthing both ends builds a ground loop that imports mains interference. Separate analogue signal cable from power runs by at least 300 mm in parallel and cross at right angles where crossing is unavoidable. Keep signal earth separate from protective earth, joined at one point; frequency converter earths follow their own rules and never borrow the signal bar. Intrinsically safe loops keep a dedicated earth bar and resistance per the certificate, never mixed with ordinary signal earths.
Terminal verification is mandatory before startup: check every point between drawing and reality with a continuity meter, tick and sign the record, and confirm transmitter polarity, channel polarity and shield terminals all agree. At energisation, measure loop current in series, expect 4 mA at zero, then compare the DCS reading with a handheld communicator and verify range configuration. The recurring traps: legacy modifications where drawings and reality diverge, causing crossed signals that eat hours, and a field side shield brushing the enclosure, which reimports the ground loop despite doing everything else right.
| Item | Rule | Consequence if broken |
|---|---|---|
| Two wire wiring | Channel powered, plus to plus | Dead loop or damaged transmitter |
| Four wire signal | Disable channel excitation first | Dual supply conflict, blown fuse |
| Shield earthing | Single end at control room | Ground loop interference |
| Distance from power | Separate trays, 300 mm parallel | Mains coupling, jumping readings |
| Terminal check | Point by point continuity versus drawing | Crossed signals eat hours |
| IS loops | Dedicated bar per certificate | Mixed earths break intrinsic safety |
Use this table for self checking and acceptance of analogue loop wiring. Identify the channel type first, earth the shield at one end, verify terminals point by point with records, and prove the loop by current plus DCS display. Retrofit projects deserve double care, since history hides between the drawing and the cabinet.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Wiring and safety per GB/T 5226.1 and IEC 60204-1; intrinsically safe loops per GB/T 3836 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.