Type S remains the reference choice for precision high temperature measurement, rated to 1600 degrees C. Yet sites still misconfigure indicators, mix up compensation cable and under-insert the assembly, throwing away the very accuracy they paid for. Here is how the pieces fit together.
The letter code defines the emf versus temperature relation. Type S is platinum-10 percent rhodium versus platinum, with the positive leg alloyed. The table in GB/T 16839.1 covers 0 to 1600 degrees C for continuous use. Its signature traits are small output, about 9.587 mV at 1000 degrees C, high stability and excellent behaviour in oxidising atmospheres; the trade-offs are price, sensitivity near 10 microvolts per degree C, and intolerance of reducing gases. The indicator must be configured as S, because a K or B setting misses by tens or hundreds of degrees.
Tolerances come in two classes. Class 1 is essentially plus or minus 1 degree C up to 1100 degrees C, then plus or minus [1+0.003(t−1100)] degrees C; Class 2 is 1.5 degrees C or 0.25 percent of reading, whichever is larger. Pick the span to match the duty: a kiln at 1300 degrees C suits type S, while continuous duty above 1600 degrees C calls for type B or radiation pyrometry. Set the indicator span to 0 to 1600 or 0 to 1760 degrees C, since too wide wastes resolution and too narrow clips data.
Use matched type S compensation cable; a K-type cable mismatched by a 10 degree C junction adds a fictitious error of over ten degrees. Keep the terminal box below 60 degrees C and never above 100. Insert the protection tube 8 to 12 times its diameter and at least 150 mm into the medium, since shallow immersion reads 1 to 3 percent low. Rhodium migration drifts the emf over the years, so calibrate critical points every 6 to 12 months.
| Code | Materials | Range and notes |
|---|---|---|
| S | Pt10Rh-Pt | 0~1600 C, precision, 9.6 mV at 1000 C |
| B | Pt30Rh-Pt6Rh | Accurate 600~1700 C, cold junction tolerant |
| K | NiCr-NiSi | 0~1100 C typical, 41 uV/C sensitivity |
| E | NiCr-CuNi | -200~800 C, highest sensitivity 68 uV/C |
| J | Fe-CuNi | 0~600 C, usable in reducing atmospheres |
| T | Cu-CuNi | -200~350 C, stable and accurate at low end |
Use this table to identify thermocouple types on site and to sanity check indicator configuration. Read the nameplate code first, verify the input configuration matches, then check compensation cable type and polarity, and finally confirm insertion depth before trusting the reading.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Graduation tables and tolerances per GB/T 16839.1 (IEC 60584-1); electrical safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.