A vortex meter reports volume at line conditions, so every shift in temperature or pressure moves the number even when nothing else changes. Compensation turns that line volume into mass or standard volume, and it is configured, installed and verified as a system, not an afterthought.
Gas density moves strongly with conditions: from 0.2 to 0.4 MPa the mass flow at the same indicated velocity nearly doubles. Standard volume is Qn = Qv multiplied by (P+101.325)/101.325 and by 293.15/(273.15+t), with P gauge in kPa and t in degrees C. Saturated steam is the special case where density depends on pressure alone, so one pressure input suffices; superheated steam and general gases need both temperature and pressure, and a missing input easily costs more than 3 percent error.
Place the pressure tap 3 to 5D downstream of the meter and the thermowell 5 to 8D downstream, inserted to the pipe centreline; anything upstream compensates the wrong operating point. Use a class A Pt100 with a transmitter loop, and size the pressure transmitter to the process ceiling, commonly 0 to 1.6 MPa. In configuration, state the reference explicitly: standard conditions are usually 101.325 kPa and 20 degrees C, though some contracts use 0, and choosing the wrong reference shifts every number by about 7 percent, an instant audit finding.
Verify the chain by hand: at steady load take three sets of t, p and Qv, compute Qn manually, and compare with the system output, chasing any disagreement above 1 percent link by link. The usual culprits are swapped tap positions, wrong reference pressure, saturated steam configured as superheated, and compensation channel ranges that do not match the actual transmitters. For custody points, put the whole compensation chain on a 12 month verification cycle and run the manual cross check monthly.
| Medium | Scheme | Key point |
|---|---|---|
| Saturated steam | Pressure only | t and p locked on saturation line |
| Superheated steam | Temperature plus pressure | Density per IAPWS-IF97 |
| General gases | Temperature plus pressure | Reference 20 C or 0 C, state it |
| Compressed air | Temperature plus pressure | Simplify only if density shift is negligible |
| Liquids | Usually none | Density shift with t is small |
| Low pressure natural gas | Temperature plus pressure | Add composition analysis for custody |
Use this table when configuring and accepting vortex metering systems. Fix the scheme by medium, place taps and thermowells per the straight run rules, state the reference in configuration, and prove the chain with a manual calculation before sign off. Monthly cross checks keep custody numbers honest.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Practice per GB/T 2624 series and IEC 60204-1; vortex verification per JJG 1029; electrical safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.