A 0-10 V signal loses accuracy with distance, and the arithmetic surprises people who never ran it. Attenuation is only half the story, because noise pickup and ground loops dominate long runs, which is why current loops rule industrial transmission.
Attenuation comes from line resistance dividing against the load: error percent is roughly Rline over the sum of Rline and Rinput, times 100. With a 100 kΩ input, even 12 ohms of cable contributes 0.012 percent, trivial; but parallel receivers collapse the impedance, three 10 kΩ instruments in parallel give 3.3 kΩ, and 20 ohms of cable then costs 0.6 percent. Estimate with 12 ohms per km for 1.5 mm² copper one way, 24 both ways: 500 m means 12 ohms round trip. Site practice caps 0-10 V at about 15 m, and anything beyond 30 m or with multiple receivers converts to 4-20 mA.
The bigger enemy is noise. A high impedance voltage source couples mains hum and switching noise easily, and long cable turns into an antenna; ground loops make it worse, because a potential difference between sending and receiving earths adds directly to the signal, and one volt is a 10 percent error. Most long run jitter is interference mislabelled as attenuation. Current loops avoid both problems: high source impedance ignores line resistance, and twisted shielded cable with single end earthing holds interference down past a kilometre, which is exactly why 4-20 mA became the industrial standard.
When the device insists on 0-10 V over distance: convert locally, with a 4-20 mA to 0-10 V isolating transmitter so the long run carries current; or lower source impedance below 10 ohms and keep receivers above 100 kΩ, never more than two in parallel without a budget check; reinforce the wiring with twisted shield, dedicated conduit and 500 mm clearance from power runs; and bond the earths to shrink potential differences. Accept by measuring the voltage difference between sending and receiving ends, chasing anything above 0.5 percent through line resistance, load and ground loop separately.
| Situation | Risk | Action |
|---|---|---|
| Under 15 m, single receiver | Negligible attenuation | Twisted shield as usual |
| 15~30 m | Visible noise coupling | Single end shield earth, clear of power |
| Beyond 30 m | Noise and ground loop dominate | Convert to 4-20 mA |
| Parallel receivers | Falling impedance amplifies error | Max two, budget the load |
| Across buildings | Earth potential adds directly | Isolating transmitter |
| Beside converters | Switching noise coupling | Isolation plus metal conduit |
Use this table when assessing 0-10 V transmission schemes. Run the attenuation arithmetic first, then the interference arithmetic over distance, earthing and environment, and convert to current or convert locally when either budget breaks. Accept with measured end to end voltage difference, locating attenuation and interference separately instead of fattening cables against noise.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Transmission and EMC per GB/T 18268 (IEC 61326); electrical safety per GB/T 5226.1 and IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.