An NPN sensor on a Mitsubishi FX3U is the classic sinking-input hookup, and everything hinges on the S/S common sitting on +24V. Current loop, wire-by-wire hookup and power-up checks below.
An NPN switch pulls the input down to 0V when conducting, so current flows from +24V into the S/S common, through the input circuit out of terminal X, along the signal wire and through the switch collector to 0V. This is sinking wiring, and it demands S/S tied to +24V; tied to 0V instead, the loop never closes and no input lights. The FX3U base unit supports both schemes, and S/S is the pivot - for NPN devices it is always +24V, the single but fatal difference from PNP wiring.
Four-step hookup for a three-wire NPN unit: brown to +24V, blue to 0V, black to the chosen X terminal, S/S to +24V. Verify three things on power-up: the X LED tracks the test piece; the black wire reads about 24V idle and drops near 0V when triggered, the NPN signature; and the program monitor for that X bit agrees with the LED. Base-unit inputs filter at roughly 10ms, fine for position confirmation, but encoder pulses must go to the dedicated high-speed counter inputs with their own filter setting - ordinary X points swallow the whole train. The commonest errors are S/S on 0V, which dead-ends every input, and reversed brown-blue, which reverse protection survives but the switch never actuates; diagnose in the fixed order of S/S voltage, black-wire voltage, then module LED. NPN and PNP devices cannot simply share one base unit since S/S takes one value only - separate modules or standardise polarity, and note the scheme on the drawing.
| Wire or terminal | Connection | Check point |
|---|---|---|
| Sensor brown | +24V | Size the supply with headroom |
| Sensor blue | 0V | Shared 0V for the sensor loop |
| Sensor black | Chosen X terminal | 24V idle, about 0V active |
| FX3U S/S | To +24V | Sinking pivot; wrong here kills everything |
| Input LED | Lights with test piece | Dark? Check S/S then polarity |
| Input filter | Default about 10ms | Fast pulses need counter inputs |
The hookup mantra for NPN on FX3U: brown positive, blue zero, black into X, and S/S to positive to close the loop. The only difference from PNP is one terminal, so think in current direction and the two schemes never blur. Verify every point with a test piece after changes and update the drawing note.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: PLC input interfaces and control circuits per GB/T 5226.1 (IEC 60204-1); proximity switch characteristics per GB/T 14048.10. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.