Explosion-proof and anticorrosion requirements for ultrasonic level transmitters

In chemical tank farms an ultrasonic level transmitter must clear two hurdles before it measures anything: the Ex certification must match the gas zone, and the wetted materials must survive the vapour above the liquid. Pick either one wrong and you end up with drifting readings or a rejected installation.

1. How it works

Match the Ex marking to the plant zone classification. Zone 0 demands intrinsic safety Ex ia IIC T4 with an associated isolator; Zone 1 accepts Ex ib or flameproof Ex d housings; Zone 2 tolerates Ex n. Always check the temperature class too: if the site gas belongs to group T3, a T4 rated transmitter keeps a safe margin. Verify every digit of the certificate against the nameplate, because a single missing code fails the acceptance inspection under GB/T 3836.1.

2. Numbers and practice

Corrosion rarely attacks the probe body first, it is the vapour above the liquid. HCl mist above hydrochloric acid tanks pits 316L within months, so specify a PTFE or PVDF radiating face; dilute alkali and marine salt atmospheres are fine with 316L plus periodic cleaning. Foaming media absorb most of the acoustic energy, and once echo amplitude drops below roughly 30 percent the instrument loses the surface entirely, so switch to guided-wave or free-space radar in those services.

3. Pitfalls and fixes

Respect the blind zone: most sensors have 25 to 50 cm of dead band directly beneath the transducer, so keep the maximum level at least the blind zone plus 10 cm away from the face. Never mount the unit above the fill point, where splash and foam swallow echoes, and shade outdoor units because direct sun at 60 degrees C can add 1 to 2 percent of thermal drift that looks exactly like instrument failure.

4. Quick selection table: Ex rating and corrosion protection

Site conditionRecommended setupDo not
Zone 0 gas atmosphereEx ia IIC T4 probe with isolatorFlameproof housings in Zone 0
Zone 1 gas atmosphereEx ib or Ex d probeTemperature class below the gas group
HCl or strong acid mistPTFE/PVDF face, flange mountBare 316L diaphragm, pits in months
Dilute alkali or salt fog316L face with periodic cleaningScale build-up absorbs the echo
Outdoor tank roofSunshade and conduit wiringDirect sun adds 1~2% drift
Foaming or heavy vapourUse radar or guided-wave radarUltrasound fails in foam

5. Notes

Use this table at the tender stage for tank farms and effluent plants. Fix the zone and temperature class first, then the wetted materials, then check the blind zone against the nozzle geometry. During acceptance, compare every Ex code on the nameplate with the certificate and reject any mismatch.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Ex equipment selection per GB/T 3836.1 and IEC 60079-0; overall machine safety per GB/T 5226.1 / IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① A temperature class below the site gas group is an ignition risk no paperwork can excuse
② Mounting above the fill point kills the echo with splash and foam, offset the nozzle instead
③ Ignoring the blind zone makes the output jump at high level and trips the interlock falsely

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.