One letter apart, but thermocouples and RTDs mount by different books: range, response, immersion depth and lead wiring all differ. Element-by-element comparison below, so each lands where it measures true.
A Type K thermocouple is self-generating - it reads the hot-junction temperature, and cold-junction compensation sets the accuracy floor; a Pt100 measures resistance, needs excitation current, and lives with lead resistance and self-heating. Direct mounting consequences: thermocouples go into fine mineral-insulated sheaths from 1.5mm diameter with fast response, ideal for dynamic and spot duty; Pt100 thin-film elements dislike stress and typically sit in 3mm or larger sheaths with slightly slower response. The range boundary: Pt100 serves about 500 degrees long-term (the element survives 850 but drifts), Type K serves 1100, so above roughly 450 degrees process temperature the thermocouple wins, while mid-low temperature precision favours the RTD.
Immersion: both need at least ten sheath diameters inserted with the sensing point past the pipe centreline, angled against the flow in fast streams. The differences: the thermocouple senses at the tip, so shallow immersion reads cold through stem conduction; the Pt100 senses over a few millimetres of film or winding with the same cold bias, but it is far more stress-sensitive - rigidly clamping both ends of the tube forces thermal expansion into the film and drifts it, so leave axial freedom. Threaded fittings need sealing and torque discipline, flanged ones the right standard and gasket rating. Wiring is the big divide: Type K demands matching compensation lead wire with correct polarity - reversed, the error doubles - and equal temperatures at both joints; Pt100 uses three- or four-wire copper cable with balanced three-wire runs, no compensation wire in play. Instruments must match: thermocouple channels need the type letter and CJC enabled, RTD channels the wire scheme and range. Never cross-wire: a Pt100 on a thermocouple channel and vice versa produce fiction. Before energising after maintenance, verify three items against the drawing - channel type, letter or range, polarity. Maintenance emphasis differs too: watch tip oxidation and drift on thermocouples, lead and terminal contact on RTDs.
| Factor | Type K thermocouple | PT100 RTD |
|---|---|---|
| Long-term range | Up to 1100 degrees | Up to about 500 degrees |
| Sheath diameter | From 1.5mm, very fine possible | Typically 3mm and up |
| Response | Fast, dynamic and spot duty | Slower, precision steady duty |
| Immersion | Ten diameters past centreline | Same, plus axial freedom |
| Wiring | K compensation wire, polarity strict | Three/four-wire copper, balanced |
| Inspection focus | Tip oxidation and drift | Lead contact and terminals |
The division-of-labour memory hook: high temperature and fast response call the thermocouple, mid-low temperature and precision call the RTD. Fill three columns in the selection sheet - medium temperature, response need, accuracy need - and the types route themselves; keep separate inspection emphases for the two families in the mounting records.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Thermocouple tables and tolerances per GB/T 16839.1 (IEC 60584-1); platinum RTDs per GB/T 30121 (IEC 60751). Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.