When the RCD starts tripping every rainy season, the device itself is usually healthy - moisture has pushed down the insulation of cables and motors. Measuring insulation in sections finds the wet spot within minutes.
A 30mA RCD trips when summed leakage approaches its threshold. Damp condensate in conduits, wet junction boxes and soaked motors drag line-to-earth insulation from tens of megohms down to 0.2~1 megohm, and a dozen such circuits together push the residual current over the limit. Trips clustered in wet periods that stop in dry weather are the classic signature of moisture, not of a faulty RCD.
De-energise, open all branch circuits, and megger each one at 500V between line and earth and between neutral and earth. Sound circuits read above 2 megohms; anything below 0.5 megohm is wet or damaged. Split the suspect circuit at its middle and test the halves until the range narrows to one box or one run. Dry wet enclosures, remake soaked cable glands, then seal conduit ends and add cabinet heaters so the moisture cannot come back.
| Check point | Pass reference | Fail sign | Action |
|---|---|---|---|
| Circuit insulation at 500V | Above 2 megohms | Below 0.5 megohm | Trace in sections, dry out |
| Conduit entries | Sealed tight | Open gaps | Seal with mastic |
| Outdoor junction boxes | IP65 or better | Water beads inside | Fit sealed boxes and glands |
| Cabinet humidity | No condensation | Wet walls, mouldy terminals | Add heater, keep vents |
| Motor winding to earth | Above 0.5 megohm | Near or below 0.5 megohm | Warm dry 2~4h, retest |
Walk this checklist before the rainy season and the RCD stops acting as a rain gauge. Always disconnect electronic equipment before megger testing, and retest after cooling to room temperature.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Residual current devices per GB/T 6829, low-voltage installations per IEC 60364 (GB/T 16895), machinery safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.