PLC restarted but the machine will not run: a fixed troubleshooting order

After a power cycle the PLC sits there and the machine does nothing - and in most cases the program is fine. Read the LEDs, check the mode, the inputs, the retentive data and the interlocks, in that order.

1. How it works

Start with the LEDs and photograph them. RUN lit means the CPU is executing - look outside. STOP lit means mode or a fatal error: check the mode switch and read the diagnostic buffer. A flashing BF is a lost network slave - wiring and slave power first. ERROR flashing with RUN off usually means program or configuration faults. The LEDs are the first evidence; touching anything before reading them wastes time.

2. Practice and pitfalls

Then work the checklist. Confirm the mode key and the startup type - some CPUs stay in STOP after power loss and need a manual start. Monitor inputs online: e-stop, guard, air pressure, oil level - an unset safety chain after restart is the single most common cause. Check retentive memory: non-retentive M areas cleared on power loss can send the program down the wrong branch, and stale retentive timers can wedge a sequence. Finally check handshake bits with the HMI or a partner PLC - a waiting step looks like a dead machine. Prevent repeats with a power-up self-check paragraph, fresh batteries every 3~5 years, and a written restart procedure.

3. Restart fault quick table

LED or symptomPoints toVerify byAction
RUN lit, machine idleField conditions unmetMonitor DI states onlineReset safety chain
STOP litMode or fatal errorDiagnostic bufferSwitch to RUN or clear fault
BF flashingNetwork slave lostCable and slave powerRestore link or replace slave
ERROR flashing, RUN offProgram or config faultBuffer fault codeFix and reload
Wrong branch after restartNon-retentive data clearedCompare pre-fault valuesRetain or add init logic

4. Notes

LEDs, mode, inputs, retentive data, interlocks - five steps, a few minutes. Reload the program only as the last resort, and back up the online copy first so field-tuned parameters survive.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Programmable controllers per GB/T 15969.2 (IEC 61131-2), control functions and fault finding per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Reloading the program before reading diagnostics: it masks hardware faults and overwrites field parameters - last resort only
② Cold-starting without clearing personnel: outputs may pulse and move parts suddenly - clear the zone first
③ Chasing software while the e-stop is unset: reset the safety chain before blaming code

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.