When a branch fault blacks out half the shop, the upstream breaker beat the branch one to it. Coordination is built from current grading, time grading and curve selection - here is how to set them up and prove them.
Current selectivity needs the upstream rating at least 1.6 times the downstream one; time selectivity needs the upstream short delay 0.2~0.3 seconds above the downstream clearing time. Two identical breakers in series have overlapping instantaneous zones, so a branch fault trips the incomer first. Before changing anything, draw the cascading diagram with every breaker model, rating and curve from the incomer down to the last miniature breaker.
Practical fixes: fit C-curve breakers (5~10 times) downstream and D-curve (10~20 times) upstream to separate the instantaneous ranges; on electronic trip units set a 0.2~0.3s short delay and enable zone selective interlocking; or use a factory-certified cascading pair where the current-limiting upstream breaker extends the downstream breaking capability. Afterwards verify that the minimum two-phase fault current still trips the branch breaker with a factor of at least 1.3, and record every setting in the log.
| Method | Typical setting | Where used | Caution |
|---|---|---|---|
| Current grading | Rating ratio 1.6 or more | Board to sub-board | Check two-phase sensitivity |
| Time grading | 0.2~0.3s per stage | Electronic trip upstream | Include downstream clearing |
| Curve grading | C below, D above | Motor circuits | Keep instantaneous ranges apart |
| Zone interlock | ZSI with 0.2s delay | Important busbars | Interlock wiring must be proven |
| Cascade pair | Per manufacturer table | Weak downstream breaking | Never mix brands freely |
Never gain selectivity by simply oversizing the upstream breaker - sensitivity to small faults is lost. Every changed setting goes into the coordination diagram, gets verified, and gets approved.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage breaker selectivity per GB/T 14048.2 (IEC 60947-2), installation design per GB 50054, machinery safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.