Acceptance checks for machine safety devices

Acceptance that waves at the safety equipment exposes every hazard after commissioning. This page provides the acceptance checklist for interlocks, light curtains, e-stops, two-hand controls and guards, each with a test method and pass criterion.

1. How it works

Start with the documents: the risk assessment (EN ISO 12100) lists the protective measures the acceptance verifies item by item; the safety circuit drawings carry their PL ratings per GB/T 16855.1; the device list names every interlock, curtain, e-stop and two-hand station; the vendor documents state response times and reset behaviour. Mismatches — an interlock on the drawing but missing on the machine, a curtain claimed where only a fence exists — are the first roadblock: fix the paperwork before testing functions. Have ready: finger and hand test rods, a stopwatch or response-time tester, a multimeter and means to simulate whole-body approach.

2. Numbers and practice

Device-by-device tests. Interlocks: the stop must trigger at a 1 mm door gap, reset only from closed, and locking interlocks must not release before full standstill. Light curtains: beam-by-beam interruption, measured response time, distance re-check, and immunity to arc light and direct sun. E-stops: every button, measured stopping time, latching and reset, reachability along the whole line. Two-hand controls: at least 250 mm between buttons, a synchronism window of 0.5 s maximum between presses, and no start from a single hand. Guards and fences: tool-required removal, mesh and height matched to their safety distance. Reset must never auto-restart the machine; an explicit start command is required.

3. Pitfalls and fixes

The acceptance runs in four passes: document check, static inspection (position, fixing, marking), functional tests as above, then fault injection — broken sensor wires, welded contacts, and behaviour while any bypass is active. Record item, standard, measured value, verdict and defect photo numbers. Missing or failed safety functions are non-conformities: rectify, retest, then sign — never accept with defects open. Hand over the device list and test records with the machine and fold them into the periodic test plan (interlocks and e-stops twice yearly, curtain response twice yearly, guards quarterly).

4. Safety device acceptance quick reference

DeviceTestPass criterionInterval
Door interlockTrigger at 1 mm gapStops at crack openingAcceptance plus half-yearly
Locking interlockLocked until standstillNo release while movingAcceptance
Light curtainBeam test plus timingAll beams, values in specAcceptance plus half-yearly
E-stop buttonsEach pressed, timedStops and latches in timeAcceptance plus half-yearly
Two-hand controlSynchronism test250 mm spacing, ≤0.5 s skewAcceptance
Guards and fencesMesh, height, fixingMatch safety distanceAcceptance plus quarterly
Reset behaviourObserve after resetNo auto-restartAcceptance
Bypass checkVerify in bypass stateKey plus time monitoringAcceptance

5. Notes

For new-machine acceptance, post-overhaul handover and annual safety reviews. The discipline: documents match hardware, every item tested — no sampling shortcuts — and defects rectified and retested before signature. Hand records over with the machine and schedule the periodic tests.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Acceptance per GB/T 5226.1 (IEC 60204-1) chapter 18 and GB/T 15706; interlocks per GB/T 18831 and guards per GB/T 8196; distances per GB/T 19876 (EN ISO 13855). Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Signing after two demo cycles: the boundary cases — gap triggering, single-hand operation, welded contacts — never surface; test every item
② Testing interlocks only fully open: a door that ignores a 1 mm gap lets a finger in without stopping; gap triggering is the hard criterion
③ Accepting with open defects to start production: a missing safety function is a non-conformity, and running before retest means running unprotected

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.