An overvoltage trip is not always the grid at fault. Fast deceleration, overhauling loads and ageing bus capacitors all push the DC link high - here is the mechanism and the fix order.
A 400V-class drive holds about 540V on the DC link (1.35 times line voltage) and trips around 780~800V. Four things push it up: grid surges or a high tap; deceleration too quick, so motor kinetic energy pumps the capacitors; overhauling loads such as hoists and decline conveyors regenerating continuously; and capacitor ageing after 8~10 years, which raises ripple and makes the bus spike sooner under the same regen.
Check in this order: if several drives trip together regardless of load, measure the input - above 415V (the plus 10 percent limit) means fix the transformer tap. If one drive trips during decel or lowering, it is regeneration: measure the bus at terminals P and N to confirm the spike, then test the braking resistor for open circuit. After a 10-minute discharge verify capacitor health - capacitance down 20 percent or bulging cases means renew the bank. For parameters, lengthen the decel time stepwise, enable overvoltage stall prevention, and for overhauling loads fit a braking unit sized from 30~50 percent of motor power, or an active front end that feeds the energy back to the grid.
| Trip pattern | Points to | Verification | Action |
|---|---|---|---|
| Several drives, any load | High grid or surge | Measure input above 415V | Tap change, add SPD |
| During deceleration | Decel time too short | Lengthen and retest | Extend decel stepwise |
| During lowering or decline | Continuous regeneration | Check resistor open circuit | Fit braking unit |
| Drive over 8 years old | Capacitor ageing | Measure capacitance, look for bulge | Renew capacitor bank |
| Random, with glitches | Sensing circuit drift | Compare real bus to display | Service the sense board |
Split grid side from load side first. Lengthening decel trades cycle time, and parameters never replace a braking unit on an overhauling load - no overvoltage is the baseline, not an option.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Adjustable speed electrical drives per GB/T 12668.2 (IEC 61800-2), insulation coordination per IEC 61800-5-1, machinery safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.