Overload is the most common servo alarm, but the alarm does not always mean a weak motor: jammed mechanics, edited parameters and tuning oscillation all masquerade as overload. This page reviews three real cases and gives a systematic troubleshooting path with numeric criteria.
Case one: a handling robot alarmed overload after six months, torque at 250 percent of rating. The cause was mechanical — debris in a linear guide created a tight spot, and push-force along the stroke varied by more than 30 percent on a dial gauge. Cleaning the carriage and regreasing cleared the alarm. Lesson: disconnect the coupling and turn the screw by hand first; heavy or uneven resistance means mechanics, and raising the torque limit only masks it until something burns.
Case two: after a drive swap, intermittent overload appeared with smooth no-load current but violently fluctuating load current. The drive torque trace showed speed-loop gains copied from another machine: a 30:1 inertia-ratio axis running high-stiffness parameters produced torque spikes that tripped overload. Restoring default gains and redoing inertia identification smoothed everything. Lesson: after any drive replacement or parameter clear, always rerun inertia identification and retune; copying old parameters is a classic trap.
Case three: a lift mechanism sized for static load ignored dynamic torque; peaks hit 135 percent of rating and the thermal model accumulated to trip within minutes. Extending acceleration from 80 ms to 200 ms brought peaks to 95 percent, and changing the gear ratio from 5:1 to 8:1 cut motor-shaft torque nearly 40 percent. Lesson: always check RMS torque — above 80 percent of rating, resize the motor or lengthen the cycle rather than trusting peak limits alone.
| Step | Check | Criterion | Action |
|---|---|---|---|
| 1 Read alarm detail | Torque percent and duration | Spike or sustained | Spike means tuning, sustained means load |
| 2 Open the mechanics | Hand-turn the screw | Smooth and light is normal | Heavy or sticky: fix mechanism |
| 3 View torque trace | Drive torque monitor | Ripple under 10 percent | Wild ripple: check gains |
| 4 Inertia ID | Rerun identification | Matches archived value | Retune if far off |
| 5 Current check | Clamp all three phases | Below nameplate rating | Above: check load and ratio |
| 6 RMS check | Equivalent torque calc | ≤80 percent of rating | Lengthen ramps or change ratio |
| 7 Temperature | Motor housing | ≤80 C (class B) | Derate if hot |
| 8 Encoder check | Feedback quality | Smooth velocity signal | Fix shield and cabling |
Iron rule for overload alarms: read the torque percentage and waveform first, split mechanics from electrics second, touch parameters last. Never simply raise the torque limit or stretch the alarm delay to clear the message — that converts an overload into a burnout.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Protection requirements per GB/T 5226.1 (IEC 60204-1); drive tuning practice per IEC 61800 adjustable-speed drive series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.