Single-point earthing is the iron rule of communication cabling: every shield and reference ground converges on one node, so ground loops cannot form. This page covers the principle, the daisy-chain versus star trade-off, and how to implement it inside a control cabinet.
A ground loop needs two or more earth points at different potentials. Single-point earthing collapses the whole system reference into one node where shields and signal references meet, so no loop exists for potential differences to drive. It suits low-frequency systems (below 1 MHz): where conductor runs are far shorter than a quarter wavelength, lead inductance is small and loop prevention is at its best. High frequencies want the opposite — nearby multi-point earthing — because long leads look inductive and the single-point structure turns high-impedance. That is why communication cables (high frequency) earth at both ends while analog circuits (low frequency) earth at one; when both coexist, isolation devices draw the boundary.
Two topologies exist. Daisy-chain: equipment grounds chained end to end to the earth point — cheap but with common-impedance coupling, since upstream current drops voltage into downstream signals; acceptable only for milliamp signal lines, never for power devices. Star: each device runs its own conductor to a central bar — more wiring, no common impedance, and the standard for control cabinets. Implementation: fit a bonding bar (PE and shield bars combined or adjacent), gather every shield, PE conductor and signal reference in a star, connect the bar at a single point to the cabinet earth plate, and run a trunk to the plant grid. Remove paint, tin the contact faces, torque M6 bolts to 8 N·m.
Field rules: terminate communication shields on the cabinet shield bar with 360-degree bonding, the far end bonding to the remote cabinets own bar, both bars tied through the trunk to the same plant grid; earth the analog 0V reference only at the PLC side, floating in the field; leave the VFD DC bus floating unless the vendor says otherwise. Three violations to hunt: shields clamped to tray supports (a second earth point), 0V earthed at both cabinets (a direct loop), and PE sharing a conductor with signal reference (power return polluting the signal ground). Each quarter, clamp every earth branch at the 100 mA range — anything above near-zero current means a second path is hiding somewhere.
| Object | Method | Location | Forbidden |
|---|---|---|---|
| Analog 0V reference | Single point | PLC-side bar | Earthing both ends |
| Comms cable shield | Both ends to own bars | Two cabinet shield bars | Clamping to tray supports |
| Equipment PE | Star collection | Cabinet PE bar | Daisy-chaining |
| VFD DC bus | Floating | No earthing | Random bonding |
| Cabinet earthing | Single point via plate | Base earth plate | Multiple random points |
| Bar terminations | M6 at 8 N·m | Paint removed, tinned | Clamping on paint |
| Branch current check | Clamp at 100 mA range | Quarterly | Ignoring any current |
| Shield bar and PE bar | Combined or adjacent | Upper cabinet area | Scattered placement |
For control-cabinet communication and signal wiring design and inspection. One line to remember: single point at low frequency, nearby points at high frequency, isolation at the boundary. Quarterly branch-current checks are the most effective way to expose hidden second earthing paths.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Earthing and bonding per GB/T 5226.1 (IEC 60204-1); EMC cabling per IEC 61800-3 and the GB/T 17626 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.