A cable tester settles cable quality in seconds, but knowing what to test, how, and what counts as good takes more than the continuity button. This page gives the full procedure for handheld testers and multimeters, pass criteria and common misjudgements.
Prepare three things. Confirm the cable ends are powered down or at least disconnected from the ports, to protect tester and equipment. Know the cable type: Cat5e/Cat6 with T568A/B ordering, PROFIBUS (green = A, red = B, shielded pair), PROFINET industrial cable — each has its own checks. Estimate the run length for the length-test calibration, and remember runs beyond 100 m exceed Fast Ethernet spec anyway. Check tester batteries (low voltage causes false opens) and either man both ends or terminate the far end before testing. On PROFIBUS, restore the terminating resistor after measurement.
Handheld tester procedure, eight-core network cable: plug both ends in, select wiremap mode and watch LEDs 1-8. Normal is sequential and synchronised; displaced order means straight-through and crossover mixing; a dark LED is a broken core; two LEDs together is a short; and pair-jumping (split pairs) only shows on testers with split-pair detection — plain continuity testers miss it entirely. Length mode: enter the NVP (around 69 percent, per the cable marking), fit the remote shorting plug, and read; the result should be within 10 percent of the installed length, with larger deviations suggesting mid-run joints or break reflections. PROFIBUS: continuity on A and B, shield-to-core insulation above 20 megohms, and certainly no A-B short.
Multimeter fallback: continuity between matching pins per T568B (white-orange, orange, white-green, blue, white-blue, green, white-brown, brown) with near-zero resistance, and pin-to-pin checks to expose shorts. Length is not directly measurable, but 24 AWG copper runs about 0.094 ohms per metre, so loop resistance divided by 0.188 estimates the run. Watch the classic traps: wiggle the plugs while testing to catch intermittent crimps; passing continuity does not prove a Cat5e link — crosstalk and return loss matter, so certify important links properly; and always check the PROFIBUS termination switch afterwards.
| Test | Instrument | Pass criterion | Meaning if failed |
|---|---|---|---|
| Wiremap | Handheld tester | 1-8 sequential, synchronised | Crossover/straight mixing |
| Continuity | Tester or multimeter | Near-zero per core | Broken core or bad crimp |
| Shorts between cores | Tester or multimeter | Open between any two | Redo the termination |
| Split-pair detection | Tester with split-pair mode | No split reported | Split pairs cause fast-ethernet errors |
| Length test | Tester length mode | Within 10 percent | Mid-run joint or break |
| Shield insulation | Multimeter or megger | Shield to core ≥20 MΩ | Damaged shield, mixed lines |
| PROFIBUS A-B | Multimeter | No short | Short stalls the bus |
| Certification | Cable certifier | NEXT and return loss in spec | Mandatory on important links |
For field testing of network, PROFIBUS and PROFINET cabling. Follow the routine: power down, select mode, check wiremap, measure length, verify shield, restore termination — no step skipped. Certify trunk and long links properly; handheld plus multimeter suffices for temporary branches.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Structured cabling acceptance per GB/T 50312; fieldbus installation per the PROFIBUS and PROFINET installation guides; electrical safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.