Analogue signals sharing a tray with power cable pick up glitches that track every motor start. Capacitive and inductive coupling explained, the spacing and shielding rules, and what to do when the tray is already full.
Two paths carry the interference. Capacitive coupling: stray capacitance between conductors injects voltage changes into the signal, worse the closer and longer the parallel run - ten metres beside 400V power is enough to rough up millivolt-level signals. Inductive coupling: magnetic fields from load current induce EMF in the loop, strongest at motor starts, and drive PWM components sneak in along shields and earth. The signature: interference synced to equipment starts, scaling with load current, with line-frequency or PWM components in the spectrum - all three together and the case is closed.
Four installation rules: separate trays or a divider, signals below power (not above - a fallen cable bridges everything); 30cm clear distance for unavoidable parallel runs, vertical crossings otherwise; shielded twisted pair for signals with the shield earthed at the control side only, and symmetrical screened cable for drive outputs earthed 360 degrees at both ends; signal earth and power earth kept separate until one bonding point. For trays that cannot be re-routed: shielded twisted pair properly earthed, a dv/dt filter or ferrites at the drive output, signal isolators to break ground loops, and software filtering as a stopgap. Closed-loop means glitches below 0.5 percent of span for 24 hours, no start-synced jumps.
| Measure | Applies to | Key points | Effect |
|---|---|---|---|
| Separate trays or divider | New work | Signals below power | Root fix |
| 30cm clearance | Unavoidable parallels | Cross vertically | Coupling drops sharply |
| Shielded pair, one-end earth | All analogue runs | Control-side earth | Baseline necessity |
| Signal isolator | Ground loops, heavy noise | One per loop | Cuts conducted path |
| Output filter, ferrites | Drive as source | Mount near the output | Trims the source |
Signals below, power above, vertical crossings, shield earthed once. One minute in the drawing review beats ten times the hours chasing noise during commissioning.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Conductors and cabling per GB/T 5226.1 clause 13, EMC installation practice per GB/T 17799 series (IEC 61000-6). Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.