One under-torqued terminal can cost a whole cabinet. This review walks through how contact resistance turns into heat, the two detection methods that catch it, and the torque discipline that stops it recurring.
A loose or oxidised terminal pushes contact resistance from a few milliohms to tens of milliohms. At 30A a 50 milliohm joint dissipates 45W continuously - a soldering iron inside the trunking. Heat accelerates oxidation, resistance climbs, and after months the spot exceeds 200C: plastic carbonises, phases flash over, dust ignites. The treachery is that the circuit keeps working and the current reads normal - only heat and a small voltage loss betray it.
Detection runs on two tools. Infrared imaging at full load is the workhorse: scan the whole board tier by tier with panels open, log any joint above 20C rise and fix anything above 40C within the week. Millivolt drop is the cross-check: across a healthy joint at 30A the drop stays under 50mV, above 100mV it gets reworked; with the board de-energised, a micro-ohmmeter flags any joint above 1 milliohm. The retrospective must answer three questions - why no torque tool, why the thermal round missed it, why it ran hot for months - and close each gap: torque values in the work instruction, paint-marked screws for the annual re-torque, quarterly thermal surveys, and a full re-torque three months after commissioning.
| Step | Standard practice | Criterion | Interval |
|---|---|---|---|
| Terminal tightening | Torque tool per marking, paint mark | M4 about 1.2~1.4N·m | On install, yearly check |
| Thermal survey | Full-load scan, tier by tier | 20C log, 40C fix | Quarterly |
| Millivolt drop | Measure across each joint | Under 50mV at 30A | Yearly |
| Contact resistance | Micro-ohmmeter, board off | Above 1 milliohm remake | With maintenance |
| New board re-torque | Full re-torque after run-in | Paint marks unmoved | 3 months after start |
Loose joints are a low-level mistake with a high-level bill. The cure is administrative: torque values written down, paint marks to prove the check, filed thermal data to show the trend - otherwise it repeats.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Assembly and testing of low-voltage switchgear per GB/T 7251.1 (IEC 61439-1), installation acceptance per GB 50171, machinery safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.