Voltage is present at the coil yet the armature stays down. In most cases the cause is undervoltage, mechanical sticking or a mixed-up coil voltage grade. Work through the steps below and the majority of cases close within minutes.
Measure the coil terminal voltage under real load conditions first. AC coils need 85~110 percent of rated voltage to pull in reliably; below that they hum or stay open. Hunt upstream for control transformer sag, burnt series contacts and thin control wiring - a couple of interposing contacts each dropping fifteen volts can starve the coil. Note that a 380V coil on a 220V circuit barely moves, and this mix-up is the most common leftover after emergency repairs.
With voltage confirmed, de-energise and stroke the armature by hand: sticking guides, greasy pole faces and broken contact carriers are the usual finds in dusty shops. Then measure coil resistance against a same-specification spare - open means a broken coil, markedly low means shorted turns with a hot coil. Finally beware phantom voltage: a high-impedance meter reads full voltage across a nearly-open control wire that cannot carry the coil current. Parallel a spare coil to prove the supply, and confirm the thermal relay and limit-switch contacts are truly closed.
| Symptom | Check point | Pass reference | Action |
|---|---|---|---|
| Coil voltage below 85 percent | Supply and series contacts | At least 187V on 220V coil | Fix joints, replace contacts |
| Voltage fine, armature sticks | Guides, pole faces, carrier | Free movement by hand | Clean faces, renew carrier |
| Coil resistance abnormal | Coil itself | Within 10 percent of spare | Replace open or shorted coil |
| Hums but will not close | Voltage grade and coil type | Nameplate matches circuit | Fit correct coil |
| New contactor still dead | Control chain contacts | All NC contacts truly closed | Trace voltage point by point |
Keep one 220V and one 380V spare coil in the toolbox. The rule is: measure voltage, stroke the armature, then measure resistance. A contactor that hums for days usually has a cracked shading ring waiting to burn the coil.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contactor operating limits per GB/T 14048.4 (IEC 60947-4-1), control circuits per IEC 60204-1 (GB/T 5226.1). Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.