Frequently asked questions on daily electrical inspection

What counts as a real inspection — how often, what is abnormal, how to record — are the questions the floor asks most. This page answers the top ten in plain form, with frequencies, criteria and recording rules.

1. How it works

Frequency and scope. Pre-shift takes two minutes on displays, sounds and smells; daily rounds run weekly in normal shops and daily in dusty or wet ones; instrumented inspections (infrared, earth resistance) run monthly to quarterly. Inspection differs from a walk-through by standardisation and traceability: a checklist executed and recorded. Scope covers what is reachable in operation — appearance, temperature, sound, indicators — never opening covers, which belongs to planned maintenance. Night shifts run the pre-shift checks folded into the shift-handover record, raising work orders on the spot rather than waiting for the day crew.

2. Numbers and practice

Judgement and action. Motor housing: comfortable to the back of a hand for 3 seconds is about 60 C; 80 C is the limit for class B, and beyond that check load and cooling. Terminal discolouration signals heat — confirm with the pyrometer, tag anything over 20 K rise, de-energise on blackening. Small fixes within reach (snugging a visibly loose terminal) are fine; anything involving de-energising, opening covers or live measurement goes through a work order. A tired fan gets reported even though the machine runs fine: a replacement fan costs one percent of a burned drive, and fan decay precedes cooling failure.

3. Pitfalls and fixes

Recording and management. A record that matters is handwritten on the spot, attaches photos and numbers for every anomaly, and feeds a monthly trend meeting. Keep the sheet to one page — anything longer gets filled carelessly — and grant inspectors written authority to stop on class-A findings without asking permission up the chain. The health check of the whole system is the order statistics: monthly work orders raised versus closed, with a closure rate under 90 percent meaning the process is idling — fix the process before adding checklist items.

4. Inspection FAQ quick reference

QuestionAnswerCriterionNote
How oftenPre-shift plus weekly plus monthlyWeekly, or daily in harsh areasScale with environment
Versus a walk-throughStandardised and traceableChecklist executedWalks leave no record
Motor housing tempHand test or pyrometer≤80 C (class B)Check load and cooling
Terminal discolourationConfirm by temperature20 K rise gets a tagBlack means de-energise
Repair authoritySnug tightness onlyNo live work, no coversEverything else on order
Anomaly recordingWork order mandatoryClosure rate ≥90 percentNo verbal handoffs
Fan noiseAlways reportEarly-warning signalCheapest prevention
Sheet fillingOn-site, handwritten, photosOne pageMonthly trend meeting

5. Notes

For training programmes and newcomer induction. The Q&A format clears the grey zones: frequencies scale with environment, authority is explicit, recording has hard requirements, and the closure rate tells you monthly whether the system is real.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Maintenance per GB/T 5226.1 (IEC 60204-1); electrical safety per GB/T 13869; motor temperature and insulation bases per GB/T 755. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Designing a three-page inspection sheet: nobody fills it honestly and it decays into ritual; one page completable in 15 minutes works
② Handing anomalies over verbally: eight of ten vanish; the closure rate is the only hard measure of whether inspection is real
③ Escalating a serious hazard instead of stopping: the approval window is when accidents happen; written stop authority for class-A findings is mandatory

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.